VELTRON DPT-
plus
Air Monitor Corporation
116-010-91.P65 (09/18/09)
VELTRON DPT-
plus
- IO&M Manual
SECTION 6 – CALIBRATION
6.4 – TRANSMITTER OUTPUT CALIBRATION (con't)
6. Once an acceptable zero reading is obtained, press and then and display will indicate:
Output 1 Span
7. Press , and display will indicate:
Output 1 Span
Perform Calibration
8. With DMM still connected as in Step 4, reading should be at maximum value of 20.00 ± 0.01mA.
9. If DMM is reading out of tolerance, use or to adjust VELTRON DPT-
plus
output for an acceptable DMM
reading.
10. Once an acceptable span reading is obtained, press and then and display will indicate.
Output 2 Zero
11.Repeat Steps 3 through 10 for Analog Output 2.
12. Press until display indicates:
Return to
MAIN MENU
13. Press and scroll Main Menu to:
EXIT
User Setup
14. Press and VELTRON DPT-
plus
will return to Normal mode of operation.
52