5.15 – TRANSDUCER SPAN SELECTION
Displays the transducer's natural span and operating span. The natural span represents the maximum process pres-
sure that the transducer can accept. The displayed natural span is for user/technician reference only and should not be
changed unless a new transducer of different natural span has been installed.
The operating span represents the calculated process pressure for a specific application, and can be adjusted 40% to
100% of the natural span.
SECTION 5 – OPERATION
43
1. While in Main Menu, use or to scroll to:
Transducer Span
Selection
2. Press to enter Transducer Span Selection menu. Display will indicate: Xdcr Natural Span
Selection
3. Press and display indicates the natural span of the installed transducer (0.05, 0.10, 0.25, 0.50, 0.75, 1.00,
1.50, 2.00, 2.50, 3.00, 5.00,10.00, 15.00, or 25.00, or 50.00, IN w.c.).
4. Use or to change setting. Once desired setting is displayed, press . New setting will be stored in
memory and display will return to Main Menu.
Caution: Only change setting if a transducer of different natural span has been installed.
Note: If user desires not to change the setting and return to Main Menu, press . Unit will remain
programmed as it was originally.
5. Use or to select remaining parameters to be changed.
6. Follow Step 4 to make any changes to parameters.
7. To return to Main Menu, select Return to MAIN MENU in Transducer Span Selection Menu and press .
Note:
If unit is configured as bi-polar, Xdcr Natural Span selections will be in the form of ±x.xx, and Xdcr
Operating Span will have a Min and Max selection.
X
- Analog Output Configuration
Transducer Span Selection
- Transmitter Input Calib.
- Xdcr Natural Span Selection
- Xdcr Operating Span Selection
- Return to MAIN MENU
Transducer Span Selection
Xdcr Natural Span
0.25 In. WC
Xdcr Operating Span
0.2500 In. WC
Return to
MAIN MENU
0.05, 0.10, 0.25, 0.50,
0.75, 1.00, 1.50, 2.00,
2.50, 3.00, 5.00, 10.00,
15.00, 25.00, 50.00,
100.00, 150.00, 200.00,
or 250.00
Adjustable from 40% to
100% of selected Natural
Span.
Default selection shown.
Available selections: