SECTION 5 – OPERATION
5.7 – TRANSMITTER SCALING & CONFIGURATION (con't)
25
9. While in Transmitter Scaling & Configuration menu, use or to scroll to:
Temperature
Configuration
10. Press to enter the Temperature Configuration sub-menu.
If Density Compensation is ON (see Process Configuration above), Input Linearization
display will indicate:
Selection
If Density Compensation is OFF display will indicate:
Temperature Off/On
Selection
11. Press and display will indicate current selection of applicable menu from Step 10.
Temperature
Off/On Selection
6
Default selection shown.
Available selections:
ON or OFF
Temperature On/Off
ON
Input Linearization
Selection
Input Linearization
OFF
Temperature
Type Selection
7
Temperature Type
Thermocouple TypeK
EXIT
Temperature Configuration
6
Available only if Density
Compensation is OFF.
ON or OFF
Minimum Temp.
Selection
Minimum Temp.
0°F
Default Temp.
Selection
9
Default Temp.
250°F
8
Temp. Fault Output
Selection
Maximum Temp.
Selection
Maximum Temp.
500°F
8
7
Available only if Input
Linearization is ON.
8 Maximum Value depends on
Temperature Type selected.
Min. plus 50 to 2000°F
Min. plus 30 to 1090°C
Min. plus 50 to 2460°R
Min. plus 30 to 1300°K
-50 to +50°F
-50 to +10°C
410 to 510°R
223 to 283°K
Thermocouple TypeE
Thermocouple Type J
Thermocouple TypeK
Themocouple Type T
100
Platinum RTD
-50 to 2000°F
-50 to 1090°C
410 to 2460°R
223 to 1300°K
Default Temperature
Drive Output High
Drive Output Low
Exits to Trans.
Scaling &
Configuration Menu
Temp. Fault Output
DEFAULTTEMPERATURE
9
Default Temperature is used when
a faulty temperature signal is
received.