5.11 – ALARM CONFIGURATION
User can turn Alarm function ON or OFF, select type of alarm (See Section 3.5 – Features for description of the different
Alarm types), and set the following values:
Low Setpoint
(this is Low, Low1, or High1 depending on Alarm Type): Selected value of transmitter span, below (for
Low and Low1) or above (for High 1) which an alarm condition will exist. Value is selected in same units as transmitter
format.
High Setpoint
(this is High, Low2, or High2, depending on Alarm Type): Selected value of transmitter span below (for
Low2) or above (for High and High2) which an alarm condition will exist. Value is selected in same units as transmitter
format.
Alarm Deadband
: Value that transmitter signal has to reach above (for Low, Low1, or Low2) or below (for High, High1,
or High2) before an activated alarm will reset. Value is selected in same units as transmitter span.
Alarm Delay
: Time between an alarm condition existing and alarm activation. Adjustable between 0.0 and 10.0
minutes in 0.1 minute increments.
33
SECTION 5 – OPERATION
- Alarm 1 Off / On Selection
- Alarm 2 Off / On Selection
- Alarm Type Selection
- Alarm 1,
Low
2
Setpt Selection
- Alarm 2,
High
3
Setpt Selection
- Alarm 1 Dead Band Selection
- Alarm 2 Dead Band Selection
- Alarm 1 Delay Selection
- Alarm 2 Delay Selection
- Return to MAIN MENU
Alarm 1 Off / On
OFF
Alarm Type
LOW / HIGH
Alarm1, Low
2
Setpt
250
[units]
Alarm2, High
3
Setpt
750
[units]
Alarm 1 Dead Band
0
[units]
Alarm 1 Delay
5.0 Min.
- Auto-Purge Configuration
Alarm Configuration
- K-Factor Configuration
User Setup Main Menu
Alarm Configuration
1
Default selection shown.
Available selections:
OFF or ON
LOW / HIGH
LOW1 / LOW2
HIGH1 / HIGH2
Depends on
Process Type
and Format
Depends on
Process Type
and Format
0.0 to 10.0 Min.
0.1 Increments
Return to
MAIN MENU
D
epends on
Process Type
and Format
Alarm 2 Delay
5.0 Min.
0.0 to 10.0 Min.
0.1 ncrements
Alarm 2 Dead Band
0
[units]
Depends on
Process Type
and Format
Alarm 2 Off / On
OFF
OFF or ON
1 Available only with Alarm option.
2
Low
,
Low1
, or
High1
depending on
Alarm Type Selected.
3
High
,
Low2
, or
High2
depending on
Alarm Type Selected.