5.12 – K-FACTOR CONFIGURATION
Caution
In the majority of applications, the use of a K-Factor is neither required nor desirable.
Before using the K-Factor feature, contact the Service Department (see Section 10) to review
the application and obtain assistance in determining the K-Factor gain and bias values.
User can turn K-Factor function ON or OFF, select a K-Factor gain value and K-Factor bias value. The K-Factor gain
is a number applied as a multiplier to the output and the K-Factor bias is an offset added to the output.
Note: If K-Factor is ON, will appear in the upper right of the display.
SECTION 5 – OPERATION
35
- Alarm Configuration
K - Factor Configuration
1
- Display Configuration
Default selection shown.
Available selections:
- K - Factor Off / On Selection
- Calculate K-Factor? Selection
- Numbr of Data Points Selection
2
- Measured Point 1 Selection
2
- Measured Point 2 Selection
2,3
- Measured Point 3 Selection
2,3
- Reference Point 1 Selection
2
- Reference Point 2 Selection
2,3
- Reference Point 3 Selection
2,3
- K-Factor Gain Value
2
- K-Factor Bias Value
2
- K - Factor Gain Selection
4
- K - Factor Bias Selection
4
- Return to MAIN MENU
K- Factor Gain
1.000
0.400 to 5.000 *
0.001 increments
K- Factor Configuration
Return to
MAIN MENU
-25.00 to 25.00%
in 0.01 increments
K- Factor Bias
0.00 %
K- Factor Off / On
OFF
OFF or ON
1 Not available if Process Type is D.P.
(see Transmitter Scaling & Config.)
2
Available only if YES is selected in Calculate
K-Factor?
3
Depends on the Number of Data Points selected.
CalculateK-Factor?
NO
NO or YES
Numbr of Data Points
One Pair
One Pair
Two Pairs
Three Pairs
Measured Point 1
1,000 CFM
Uses Process Units
& Format Selected
in Process Config.
Measured Point 2
5,000 CFM
Uses Process Units
& Format Selected
in Process Config.
Measured Point 3
9,000 CFM
Uses Process Units
& Format Selected
in Process Config.
Reference Point 1
1,000 CFM
Uses Process Units
& Format Selected
in Process Config.
Reference Point 2
5,000 CFM
Uses Process Units
& Format Selected
in Process Config.
Reference Point 3
9,000 CFM
U
ses Process Units
& Format Selected
in Process Config.
4
Available only if NO is selected in Calculate
K-Factor?
K-Factor Gain
XXXX
K-Factor Bias
XXX %
User Setup Main Menu
Gain is calculated
from data entered
above.
Gain is calculated
from data entered
above.
*Available range depends
on operating span versus
natural span.
K on