5.6 – CONFIGURATION PROGRAMMING
Note:
User selectable parameters are limited to standard features and those available for options installed at the
factory. The following will detail all user parameters, which may or may not be available on your unit.
With power ON and initialization complete (see Section 5.2), press and display will indicate:
USER SETUP
Pressing will enter the user into the Main Menu of configuration programming. The display will indicate:
Transmitter Scaling
and Configuration
By using and , the user can scroll through the following selections:
SECTION 5 – OPERATION
MAIN MENU SELECTION
Transmitter Scaling & Configuration
Low Pass Filter Selection
AUTO-zero Configuration
AUTO-purge Configuration
Alarm Configuration
K-Factor Configuration
Display Configuration
Analog Output Configuration
Transducer Span Selection
Transmitter Input Calibration
Transmitter Output Calibration
Transducer Characterization Selection
Display Internal Temperature
Perform Transmitter Reset
Exit User Setup
DESCRIPTION
Allows for the configuration of process variable such as: Density Compensation
Type, Square root, process type, process minimum/ maximum/units, duct area,
percent lockdown, and Temperature configuration. Also offers a Flow/D.P. calculator
that allows user to calculate maximum flow or differential pressure based on
entered variables.
Selects amount of filtering applied to transducer output.
Turns AUTO-zero function ON or OFF, and selects activation interval.
Refer to AUTO-purge Installation, Operation & Maintenance Manual for
configuration information.
Turns alarm function ON or OFF, select Alarm Type, High and Low Setpoints,
Deadband selection, and Alarm Delay.
Turns K-Factor ON or OFF, and allows for the calculation or selection of gain and
bias values.
Allows for the configuration of Display Parameters and Filters.
Allows for the selection of Analog Output 2 parameter.
Allows for displaying the natural span of the installed transducer, and selecting the
operating span.
Allows for the zeroing and spanning transmitter analog Inputs.
Allows for the zeroing and spanning of transmitter analog Outputs.
Allows transducer characterization data to be entered when transducer is replaced.
Allows for displaying the internal temperature of the VELTRON DPT-
plus
unit.
Allows for restarting the transmitter in case of lock-up.
Returns display to
Normal
operation.