Ventilation Mode
This mode is designed to control ridge vents and side-wall curtains for cooling. Multiple stages can be con-
figured to open the vent in increments according to the temperature.
Override positions for high light intensity and weather alarms can also be configured to actively adjust the
position depending on conditions if desired. To enable a position option, turn on the appropriate switch and
the settings will be shown.
Shade mode will reduce the %open position in the solar shading and temperature shading modes in an
effort to reduce solar radiation resulting in excess heat. Shading from high intensity light can reduce solar
heating or when the interior temperature is too high can help alleviate excess heat.
1. Solar Venting
Set this option to limit the position based on light intensity.
If intensity is high, the shade will reduce %open to the selected position.
2. Light Sensor Select the sensor to read the light intensity.
3. Solar Position
Maximum %open position when limit is exceeded.
4. Solar Limit
Light intensity high limit; if reached, the position limit is activated.
5. Temperature Staging
Set this option to limit the position based on high temperature.
If temperature is high, the shade will reduce %open to the selected position.
6. Temperature Sensor
Select the sensor to read the temperature.
7. Position Range First and Final temperature stage positions.
8. First Stage Temperature First temperature stage activation; move to first stage position.
9. Number of Stages
Select how many stages to break the position movements into.
10. Stage Separation
Degrees between ventilation stages.
Separation is used both when rising and falling to segregate stage reversal.
2
3
4
6
7
8
1
5
9
10