Table 5-5: Combination Mode Settings
Menu Option
Setting
Boiler Mode
Combination
Remote Signal
Network
Internal Setpt
40°F to 190°F
Refer to section 3.3 for instructions on changing menu options.
While it is possible to change other temperature-related functions for combination mode, these
functions are preset to their factory default values. These default settings work well in most
applications. It is suggested that AERCO be contacted prior to changing settings other than the
unit’s setpoint. For a complete listing of temperature related function defaults, see Appendix E.
To set the unit to the manual mode, press the
AUTO/MAN
switch. The
MANUAL
LED will light.
To set the unit back to the auto mode, press the
AUTO/MAN
switch. The
MANUAL
LED will go
off and the
REMOTE
LED will light.
When the boiler is switched to ACS control, the ACS controls the valve position. There are no
setup requirements to the boiler(s) in this mode.