Table 3-4: Configuration Menu
*NOTE
The Bldg Ref Temp and Reset Ratio Menu Items are only
displayed when the Outdoor Sensor is set to “Enabled”.
Menu Item Display
Available Choices or Limits
Default
Minimum
Maximum
Internal Setpt
Lo Temp Limit
Hi Temp Limit
130°F
Unit Type
KC Boiler, KC Boiler LN,
BMK Blr Std, BMK Blr Std Dual,
BMK Blr LN, BMK Blr LN Dual
KC Water Heater,
KC Water Heater LN,
Innovation WH
BMK Blr LN
Unit Size
(Only the unit sizes
available for the Unit
Type will be displayed)
750 MBH, 1000 MBH,
1500 MBH, 2000 MBH,
2500 MBH, 3000 MBH,
6000 MBH
750 MBH
or
1000 MBH
Fuel Type
Natural Gas, Propane
Natural Gas
Boiler Mode
Constant Setpoint,
Remote Setpoint,
Direct Drive,
Combination,
Outdoor Reset
Constant Setpoint
Remote Signal
(If Mode = Remote
Setpoint, Direct Drive
or Combination)
4 – 20 mA/1 – 5V
0 -20 mA/0 – 5V
PWM Input (Legacy BMS),
Network
4 – 20 mA,
1-5V
Outdoor Sensor
Enabled or Disabled
Disabled
*Bldg Ref Temp
(If Mode = Outdoor
Reset)
40°F
230°F
70°F
*Reset Ratio
(If Mode = Outdoor
Reset)
0.1
9.9
1.2
*System Start Tmp
(If Outdoor Sensor =
Enabled)
30°F
100°F
60°F
Setpt Lo Limit
40°F
Setpt Hi Limit
60°F
Setpt Hi Limit
Setpt Lo Limit
210°F
140°F
Temp Hi Limit
40°F
210°F
160°F