Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 4 – INITIAL START-UP
Page
66
of
192
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0082_0J
05/21/2014
Ph.: 800-526-0288
GF-130
Figure 4-4: Over Temperature Limit Switch Locations
4.6.1 Digital Alarm Switch Checks and Adjustments
The digital alarm switch settings can be checked or adjusted using the controls and display on
the front panel of the switch illustrated and described in Figure 4-5.
F
Alarm
RST
SET
Limit Control
Figure 4-5: Digital Alarm Switch Front Panel
PARTIAL FRONT VIEW WITH PANEL REMOVED
Digital Over-
Temperature
Limit Controller
Reset button for
Manual Temperature
Limit Switch
Manual
Temperature
Limit Switch
Adjustable
Temperature
Limit Switch
(auto-rest)