Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual
APPENDIX E – BOILER DEFAULT SETTINGS
OMM-0082_0J
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
Page
155
of
192
GF-130
Ph.: 800-526-0288
05/21/2014
APPENDIX E – BOILER DEFAULT SETTINGS
MENU & OPTION
FACTORY DEFAULT
Setup Menu
Password
0
Language
English
Unit of Temp
Fahrenheit
Comm Address
0
Baud Rate
9600
Configuration Menu
Internal Setpt
130°F
Unit Type
BMK Boiler LN
Unit Size
750 MBH or 1000 MBH
Fuel Type
Natural Gas
Boiler Mode
Constant Setpoint
Remote Signal (If Mode = Remote
Setpoint, Direct Drive or Combination)
4 – 20 mA / 1-5V
Bldg Ref Temp
(If Boiler Mode = Outdoor Reset)
70°F
Reset Ratio
(If Boiler Mode = Outdoor Reset)
1.2
Outdoor Sensor
Disabled
System Start Tmp
(If Outdoor Sensor = Enabled)
60°F
Setpt Lo Limit
60°F
Setpt Hi Limit
195°F
Temp Hi Limit
195°F
Max Valve Position
100%
Pump Delay Timer
0 min
Aux Start On Dly
0 sec
Failsafe Mode
Shutdown
Analog Output
Valve Position 0-10V
CAUTION: DO NOT Change
Lo Fire Timer
2 sec