Condensate Drain Trap Maintenance
–
Continued
NOTE
T
here are two slightly different types of condensate traps that may
be used in your configuration; an older style with a separate inlet
adapter, and a newer style with a built-in adapter (see Figure 7-6).
Maintenance is the same, except that the newer style does not
need an orifice gasket (Step 7).
Figure 7-6: External Condensate Trap
THUMB
SCREWS
COVER
GASKET
FLOAT
GUIDE
FLOAT
CONDENSATE
TRAP
(P/N 24060)
OUTLET
Condensate
Trap O-Ring
Float
Float Guide
O-Rings
(2)
3/4" NPT
Thumb Screws
(4)
INLET
Adapter
Opening