Benchmark 750/1000 Boiler Installation, Operation & Maintenance Manual
CHAPTER 7 – MAINTENANCE
Page
92
of
192
AERCO International, Inc.
•
100 Oritani Dr.
•
Blauvelt, NY 10913
OMM-0082_0J
05/21/2014
Ph.: 800-526-0288
GF-130
Igniter-Injector Replacement
–
Continued
Figure 7-3: Igniter-Injector Orientation (Looking Down from Above)
10. Reinstall the igniter-injector in the burner plate. Torque to
170 - 180 in-lbs
. DO NOT over
tighten.
11. Connect the staged ignition assembly to the gas injector tube of the igniter-injector by
securing the compression nut to the elbow of the staged ignition assembly.
12. Reconnect the igniter-injector cable.
13. Reinstall the shroud on the unit.
7.3 FLAME DETECTOR REPLACEMENT
The flame detector (P/N 24356-1) is located on the burner plate at the top of the unit (see Figure
7-1 and
Figure 7-2
). The flame detector may be hot. Allow the unit to cool sufficiently before
removing the flame detector. Inspect or replace the flame detector as follows:
Flame Detector Replacement
1. Set the
control panel
ON/OFF
switch to the
OFF
position. Disconnect AC power from the
unit.
2. Remove the top shroud from the unit by grasping the top handle and lifting straight up.
This will disengage the shroud from the four (4) pins in the side panels.
3. Disconnect the flame detector lead wire.
4. Remove the two (2) screws securing the flame detector to the plate (Figure 7-2 on
previous page). The flame detector is secured to the burner plate with one #10-32 screw
and one #8-32 screw.
5. Remove the flame detector and gasket from the burner plate.
6. Thoroughly inspect the flame detector. If eroded, the detector should be replaced.
Otherwise clean the detector with a fine emery cloth.
7. Reinstall the flame detector and flame detector gasket.
8. Reconnect the flame detector lead wire.
9. Reinstall the shroud on the unit.
INJECTOR TUBE
120°
INJECTER-IGNITOR
INJECTOR TUBE
ANGLE
BURNER PLATE
BLOWER