Overvoltage Fault
600 SERIES
The inverter has two DC inputs,
DC1
and
DC2
, each of which is limited to 500 V. A
relay (combiner) inside the inverter connects the two arrays, in series, upon
activation. This doubles the voltage level inside the inverter.
A symmetry controller balances the voltages of the two terminals, positive of
DC1
and negative of
DC2
, so they do not exceed 500 V with respect to ground under any
condition. If the controller detects an asymmetry, the controller shuts down the
inverter. When the inverter shuts down the relay opens, which connects the arrays
back into the parallel configuration, limiting the voltage of any array conductor (with
respect to ground) to 500 V.
In the rare instance of a failure of the combiner relay, the two arrays will be left
connected in series even with the inverter deactivated. Since the symmetry controller
does not operate in this condition, there is the possibility of the voltage of an array
terminal to ground exceeding 500 V. The inverter detects this fault condition and
displays the message
ARRAY OVERVOLTAGE
.
1000 SERIES
The 1000 series is limited to 1000 VDC maximum. If the inverter detects more than
1000 V with respect to ground, it will shut down. The inverter will display an
ARRAY OVERVOLTAGE
error.
TO RESOLVE AN OVERVOLTAGE FAULT
If an
ARRAY OVERVOLTAGE
message is displayed on the screen, complete the
following steps:
1. Turn the DC disconnect switch to the
OFF
position.
2. Contact AE Solar Energy Technical Support.
Inverter Faults
The following table lists the inverter faults. If the
FAULT
LED is lit, check the
display message and take the appropriate action
Advanced Energy® AE 3TL Inverters
570-1003552-05A
Troubleshooting and Solar Energy Technical Support
9‑5
Содержание AE 3TL 1000 Series
Страница 2: ......
Страница 12: ...Advanced Energy xii 570 1003552 05A List of Tables...
Страница 14: ...Advanced Energy xiv 570 1003552 05A List of Figures...
Страница 26: ...Advanced Energy 1 12 Safety and Product Compliance Guidelines 570 1003552 05A...
Страница 64: ...Advanced Energy 4 28 Installing 570 1003552 05A...
Страница 86: ...Advanced Energy 6 4 Operating the Arc Fault Detection Unit 570 1003552 05A...
Страница 92: ...Advanced Energy 7 6 Data Monitoring and Controls 570 1003552 05A...
Страница 110: ...Advanced Energy 9 14 Troubleshooting and Solar Energy Technical Support 570 1003552 05A...
Страница 116: ...Advanced Energy A 6 Specifications 570 1003552 05A...
Страница 118: ...Figure 11 2 AE 3TL mechanical diagram Advanced Energy B 2 System and Mechanical Diagrams 570 1003552 05A...
Страница 120: ...Advanced Energy B 4 System and Mechanical Diagrams 570 1003552 05A...