Figure 5‑7. Previous day's feed-in power
3. Press the
ESC
button to return to the basic operating screen.
The inverter stores data which records measured values while the inverter is
running. The default configuration includes 16 measurement channels.
Table 5‑4. Data storage
Logging Cycle
Length of Storage Time
1 minute
6 months
5 minutes
2.5 years
10 minutes
5 years
CONFIGURING THE INVERTER
The following configuration settings can be set up or modified:
• Date and time
• Menu language
• Communication options
• Portal settings
To Enter the Password
The inverter password is required to configure the inverter and to make changes to
the parameters.
☞
Important
The default password is set at the factory to 72555.
1. Press the
F1
button to display the main menu.
2. Press the ▼ button until
Configuration
is highlighted and press the enter
button.
3. Press the ▼ button until
Password
is highlighted and press the enter button.
The
Password Input
screen displays.
Advanced Energy® AE 3TL Inverters
570-1003552-05A
Operating
5‑13
Содержание AE 3TL 1000 Series
Страница 2: ......
Страница 12: ...Advanced Energy xii 570 1003552 05A List of Tables...
Страница 14: ...Advanced Energy xiv 570 1003552 05A List of Figures...
Страница 26: ...Advanced Energy 1 12 Safety and Product Compliance Guidelines 570 1003552 05A...
Страница 64: ...Advanced Energy 4 28 Installing 570 1003552 05A...
Страница 86: ...Advanced Energy 6 4 Operating the Arc Fault Detection Unit 570 1003552 05A...
Страница 92: ...Advanced Energy 7 6 Data Monitoring and Controls 570 1003552 05A...
Страница 110: ...Advanced Energy 9 14 Troubleshooting and Solar Energy Technical Support 570 1003552 05A...
Страница 116: ...Advanced Energy A 6 Specifications 570 1003552 05A...
Страница 118: ...Figure 11 2 AE 3TL mechanical diagram Advanced Energy B 2 System and Mechanical Diagrams 570 1003552 05A...
Страница 120: ...Advanced Energy B 4 System and Mechanical Diagrams 570 1003552 05A...