Table 9‑1. Inverter faults
Display Screen Text
Operation Condition
Description
ACTIVATION LT
Timeout. Intermediate circuit
is precharging.
1. Acknowledge the
fault by pressing the
ESC
button and de-
energizeing the
inverter.
2. Contact AE Solar
Energy Technical
Support if this fault
reoccurs.
ACTIVATION LT 1
Failure of a power branch in
the boost converter.
ACTIVATION LT 2
Drop of intermediate circuit
voltage below limit value
P0024.0 (power section).
ACTIVATION LT 3
Setpoint value for
intermediate circuit
symmetrization faulty.
ACTIVATION LT 4
Timeout. Intermediate circuit
symmetrization.
AFI FAULT
Fault current detection (ENS,
power section).
Arc Fault Interrupt (AFI)
sensor failed.
1. Check the PCB
contact.
2. Contact AE Solar
Energy Technical
Support to replace.
AFI WARNING
An insulating fault was
detected during the system's
automatic insulation test
(ENS, power section).
Check the system's
insulation and repair.
COMMUNICATION LT
Communication problem
between control system and
power section.
1. Acknowledge the
fault by pressing the
ESC
button and de-
energizeing the
inverter.
2. Contact AE Solar
Energy Technical
Support if the fault
occurs again.
CONTROLLER VOLTAGE 1
Boost converter of the
positive intermediate circuit
could not regulate
sufficiently.
Wait until the controller
has restabilized.
CONTROLLER VOLTAGE 2
Boost converter of the
negative intermediate circuit
could not regulate
sufficiently.
Wait until the controller
has restabilized.
Advanced Energy
9‑6
Troubleshooting and Solar Energy Technical Support
570-1003552-05A
Содержание AE 3TL 1000 Series
Страница 2: ......
Страница 12: ...Advanced Energy xii 570 1003552 05A List of Tables...
Страница 14: ...Advanced Energy xiv 570 1003552 05A List of Figures...
Страница 26: ...Advanced Energy 1 12 Safety and Product Compliance Guidelines 570 1003552 05A...
Страница 64: ...Advanced Energy 4 28 Installing 570 1003552 05A...
Страница 86: ...Advanced Energy 6 4 Operating the Arc Fault Detection Unit 570 1003552 05A...
Страница 92: ...Advanced Energy 7 6 Data Monitoring and Controls 570 1003552 05A...
Страница 110: ...Advanced Energy 9 14 Troubleshooting and Solar Energy Technical Support 570 1003552 05A...
Страница 116: ...Advanced Energy A 6 Specifications 570 1003552 05A...
Страница 118: ...Figure 11 2 AE 3TL mechanical diagram Advanced Energy B 2 System and Mechanical Diagrams 570 1003552 05A...
Страница 120: ...Advanced Energy B 4 System and Mechanical Diagrams 570 1003552 05A...