The PV array Equipment Grounding Conductor (EGC) must be connected to the
GND stud bolt available in the inverter connection box.
The neutral conductor on the AC side of the system must be connected and solidly
grounded to the X0 terminal of the service transformer.
Monitoring
If Ethernet communications are used (typically with REFUlog), ensure that each
inverter has been assigned a different IP address and the protocol is set to "0".
If RS-485 communications are used (typically with 3rd party monitoring software),
ensure that each inverter has been assigned a different USS address and the protocol
is set to "1".
Startup
All equipment covers are closed before startup.
Close the AC system circuit breakers or insert the external main fuse.
Turn the DC disconnect to the ON position.
Advanced Energy
C‑2
Inverter Startup Checklist
570-1003552-05A
Содержание AE 3TL 1000 Series
Страница 2: ......
Страница 12: ...Advanced Energy xii 570 1003552 05A List of Tables...
Страница 14: ...Advanced Energy xiv 570 1003552 05A List of Figures...
Страница 26: ...Advanced Energy 1 12 Safety and Product Compliance Guidelines 570 1003552 05A...
Страница 64: ...Advanced Energy 4 28 Installing 570 1003552 05A...
Страница 86: ...Advanced Energy 6 4 Operating the Arc Fault Detection Unit 570 1003552 05A...
Страница 92: ...Advanced Energy 7 6 Data Monitoring and Controls 570 1003552 05A...
Страница 110: ...Advanced Energy 9 14 Troubleshooting and Solar Energy Technical Support 570 1003552 05A...
Страница 116: ...Advanced Energy A 6 Specifications 570 1003552 05A...
Страница 118: ...Figure 11 2 AE 3TL mechanical diagram Advanced Energy B 2 System and Mechanical Diagrams 570 1003552 05A...
Страница 120: ...Advanced Energy B 4 System and Mechanical Diagrams 570 1003552 05A...