AVERTISSEMENT:
Prendre les mesures de précaution adéquates; cette partie contient de
hautes tensions pouvant causer des blessures graves ou entraîner la mort.
WARNING:
All electrical installations should be completed in accordance with national
and local electrical codes. The inverter must be connected to a dedicated
circuit with no other outlets or devices connected to the same circuit.
AVERTISSEMENT:
Tous les travaux électrique doivent être effectués conformément aux codes
de l’électricité national et local. L’onduleur doit être branché sur un circuit
dédié ne comprenant aucune autre sortie ou aucun autre dispositif
connecté(e) au même circuit.
Observe the following requirement when selecting the DC conductor:
• Use 12 AWG to 8 AWG (4 mm² to 10 mm²) copper wire, rated for 90°C
(194°F)
DC conductors should be installed per NEC 690.35.
The inverter should not exceed the following operating data regardless of the
operating circumstances:
Table 4‑2. Maximum DC operating data
Maximum per Fuse Bank
12kW
16kW
20kW
23kW
DC voltage
600 series: 500 V
1000 series: 1000 V
DC operating current
27.5 A
33.0 A
37.5 A
40.0 A
DC Connections
DANGER:
Electrical connections must comply with national and local standards.
Voltage drop and other considerations may dictate that larger wire sizes be
used.
Advanced Energy
4‑16
Installing
570-1003552-05A
Содержание AE 3TL 1000 Series
Страница 2: ......
Страница 12: ...Advanced Energy xii 570 1003552 05A List of Tables...
Страница 14: ...Advanced Energy xiv 570 1003552 05A List of Figures...
Страница 26: ...Advanced Energy 1 12 Safety and Product Compliance Guidelines 570 1003552 05A...
Страница 64: ...Advanced Energy 4 28 Installing 570 1003552 05A...
Страница 86: ...Advanced Energy 6 4 Operating the Arc Fault Detection Unit 570 1003552 05A...
Страница 92: ...Advanced Energy 7 6 Data Monitoring and Controls 570 1003552 05A...
Страница 110: ...Advanced Energy 9 14 Troubleshooting and Solar Energy Technical Support 570 1003552 05A...
Страница 116: ...Advanced Energy A 6 Specifications 570 1003552 05A...
Страница 118: ...Figure 11 2 AE 3TL mechanical diagram Advanced Energy B 2 System and Mechanical Diagrams 570 1003552 05A...
Страница 120: ...Advanced Energy B 4 System and Mechanical Diagrams 570 1003552 05A...