DC1+ inputs
DC2+ inputs
DC1- inputs
DC2- inputs
Figure 4‑10. 600 series DC input terminal blocks in the connection box
DC- inputs
DC+ inputs
Figure 4‑11. 1000 series DC input terminal blocks in the connection box
8. For the 600 series, ensure that the same number of strings are installed in DC1
and DC2 inputs.
9. Tighten each screw terminal to 2.5 Nm (22 lbf-in).
10. Pull test each conductor.
AC Conductors
DANGER:
Electrical connections must comply with national and local standards.
Voltage drop and other considerations may dictate that larger wire sizes be
used.