– 106 –
Relay Type
Enter 0 for polling loop trigger or relay. Enter 1 for 4204 relay
outputs. Enter 2 for Powerline Carrier devices. Press
✴
to
continue.
V-PLEX ZONE
#
For polling loop trigger outputs (4208UXM)/4101SN), enter the
protection zone number (010-128) linked to each output, if used. If
not using a protection zone on these modules, enter the relay zone
number (601-696). Be sure to enroll the module’s serial number (see
Zone Programming ZONE NUMBER prompt). Press
✴
to continue.
ECP ADDRESS
For relay module (4204) outputs, enter the actual relay module's
address (01-15) as set by its DIP switches.
MODULE
RELAY #
For 4204 relay outputs, enter the specific relay number on that
module (1-4). Press
✴
to continue.
House Code
For Powerline Carrier devices, enter the numerical equivalent of the
House Code of the device as follows:
A=00
E=04
I=08
M=12
B=01
F=05
J=09
N=13
C=02
G=06
K=10
O=14
D=03
H=07
L=11
P=15
Unit Code
Enter the numerical unit code of the Powerline Carrier device (00-31).
Press
✴
to continue.
The keypad will display the Start and Stop summary screens again.
Press
✴
to continue.
3.
When all relays have been programmed, enter 00 at the "ENTER RELAY NO." prompt.
4.
If defining a Zone List, continue to the next procedure in this section. If not, enter 00 +
✴
at the next two prompts. Then enter *99 to exit programming completely. After
exiting, enter the [Installer Code] + OFF to cancel the system's settling delay.
5.
If supervision of the relay is desired, enter a response type for the relay's corresponding
supervisory zone. This is equal to 6 + 2-digit relay number. For example, if you are
programming relay no. 1, the relay's supervisory zone would be 601. Programme this
zone for response type 19 (24 hr. trouble) or 05 (trouble by day, alarm by night) in #93
Programming Mode.
Zone List Programming
After all relays have been programmed, upon entering 00 at the "ENTER RELAY NO."
prompt, you will be asked to enter a Zone List. If a Zone List number was used to start/stop
a relay, you must define the zones belonging to that list:
Enter Zone LIST
00=QUIT 00
Enter the zone list number 01-15. Enter 00 to quit.
001 Enter Zn Num.
000=QUIT 000
Using three-digit entries, enter each zone to be included in this
zone list. Press
✴
after each zone number is entered. When all
zones have been entered, enter 00, then press
✴
001 Del Zn LIST?
0=No 1=Yes
Enter 0 to save the zone list entered. Enter 1 to delete that zone
list.
001 Delete Zone?
0=No 1=Yes
Enter 1 to delete one or more zones in that zone list. Enter 0 if no
changes are necessary. If 1 is entered, the next screen will appear,
otherwise the "Enter Zone List" prompt will reappear.
001 Zn to Delete?
000=QUIT 000
Enter each zone number to be deleted from the zone list, pressing
✴
after each number.
Содержание VISTA-120
Страница 2: ...THANK YOU For Choosing Ademco s Vista 120...
Страница 9: ...1 PART 1 HARDWARE INSTALLATION PROCEDURES...
Страница 72: ...64 PART 2 PROGRAMMING THE SYSTEM...
Страница 151: ...143 PART 3 SYSTEM OPERATION AND TESTING...