– 95 –
At any time during this step, you may press the [*] key on the keypad or the upper left-hand
button of the programme tool if you are satisfied with the serial and loop number
combination that has been enrolled, regardless of whether or not the enrolled input has
been "confirmed." This will ready the system to enroll the next serial number device.
If the incorrect device has been enrolled, press the [#] key on the keypad or the upper right-
hand button of the programme tool to delete the serial number and return to the "LEARN
S/N" prompt. A single long beep will be heard from the keypad to verify pressing of the
upper right-hand button. Then, press "1" (Yes) or press the upper left-hand button of the
programme tool (a single short beep will verify the system is ready for enrolling) and re-
activate the proper device or device loop input.
When you have finished programming all zones, test each using the system's TEST mode.
Do not use the Transmitter ID Sniffer mode for this, as it will only check for transmission of
one zone on a particular transmitter, NOT the zones assigned to each additional loop, and
will NOT verify polling loop type.
Report Code Programming
All report codes are entered using #93 menu mode programming, either through Report
Code Programming, or through the Zone Programming mode while entering other zone
information. In the Vista-120, reports are divided into six categories. These categories
represent the main menu options found in the Report Code Programming mode. Reports and
the categories in which they are found are as follows:
ALARM CODES
RESTR, SUPV. CODES
SYSTEM GROUP #1
(for groups of 16 zones)
Zone Alarm Reports
Alarm Restore
Closing (arm away)
Trouble
Opening (disarm)
Trouble Restore
System Low Battery
Bypass
Low Battery Restore
Bypass Restore
AC Mains Loss
AC Mains Restore
Periodic Burg. Test
Power
Cancel
Programme Tamper
Callback Request
SYSTEM GROUP #2
SYSTEM GROUP #3
Arm Stay Early Open
Time Set, Log Reset
Early Close
Log 50%, 90% Full
Late Open
Event Log Overflow
Late Close
Autobypass by Zone
Failed to Open
Autobypass by User
Failed to Close
Recent Close
Auto-Arm Failed
Schedule Change
The programming sequence that follows assumes that you will be entering all reports for the
system at one time. In actuality, you may skip from one main menu option to another by
pressing 0 (N) to each main menu option. Main menu options are highlighted in bold text.
To enter report codes, do the following:
Enter Programme mode [Installer Code] + 8 0 0 0. Then press #93. Enter (N) to the main
menu options until the Report Code Programming option is displayed.
REPORT CODE PROG
1 = YES 0 = NO 0
Press 1 (Y) to enter to Report Code Programming
mode.