VISTA-10SE Installation and Setup Guide
6–4
PROMPT
VALID ENTRIES
EXPLANATION
02 Stop:
Zn List
No List
0
STOP by Zone List
[
✱
]
to continue
If a zone list will be used to STOP, or restore, the relay action,
enter the zone list (ZL) number 1, 2, or 3 (to be programmed in
✱
81 mode). If not used, enter 0.
02 Stop:
Zn Typ
Not Used
00
STOP by Zone Type
[
✱
]
to continue
If a zone type or system operation will be used to STOP the relay
action, enter the appropriate two digit code (see the "ZT" choices
listed above). If not, enter 00.
02 A EV ZL ZT –
STT 0 0 0 00 –
START Summary Screen
[
✱
]
to continue
This screen displays a summary of the current relay START
programming.
02 A EV ZL ZT –
STP 0 0 0 00 –
STOP Summary Screen
[
✱
]
to continue
This screen displays a summary of the current relay STOP
programming.
E n t e r R e l a y N o .
( 0 0 = Q u i t ) 0 1
The display then returns to the first screen so that the next relay number to be
programmed can be entered, unless you enter [0][0] to end relay programming.
Previously entered data can be reviewed by pressing [#] [8] [0]. After the relay number is
chosen, press [
✱
] to go to the next screens. This is a review mode only, and data cannot be
changed.
Example of Relay Programming
A lamp is to be turned on when any one of three specific zones are faulted or when any 24-hour
auxiliary zone is faulted. We want to turn off the lamp manually without affecting the arming
status of the system.
In field
✱
80, we choose Relay 01 and program the Action (A) to be "2" (Close and stay closed). The Event we
are looking for to START the relay action is a fault, so we program "2" in (EV). We will use Zone List 1 for
the 3 specific zones, so we program "1" in (ZL), (these 3 zones are programmed in field
✱
81's Zone List 1).
The second condition for turning on the indicator is triggering a 24-hour auxiliary zone (Zone Type 08), so we
program (ZT) as "08."
To STOP relay action and turn off the indicator, we do not want to use a restore of any zone, so we will
program a "0" for the "Restore of" Zone List (ZL). To choose a manual entry of User Code + [#] + [7] to turn it
off, we will program (ZT) as "34."
If no other relay is to be programmed, we go to field
✱
81 and program the 3 specific zones in Zone List 1.
Press
✱
81. (Zone Lists for Output /Relays). This interactive mode is applicable only if you have programmed
✱
80 mode.
Refer to, OUTPUT RELAYS WORKSHEET FOR FIELDS
✱
80 and
✱
81 in the Programming Form, to
record data.
Содержание VISTA-10ES
Страница 24: ...VISTA 10SE Installation and Setup Guide 3 4...
Страница 34: ...VISTA 10SE Installation and Setup Guide 4 10...
Страница 44: ...VISTA 10SE Installation and Setup Guide 5 10...
Страница 58: ...VISTA 10SE Installation and Setup Guide 9 4...
Страница 66: ...VISTA 10SE Installation and Setup Guide 11 6...
Страница 68: ...VISTA 10SE Installation and Setup Guide 12 2...
Страница 80: ...1 9 l N7227V6 7 01 165 Eileen Way Syosset New York 11791 Copyright 2001 PITTWAY CORPORATION...