
VISTA-10SE Installation and Setup Guide
11-2
Go/No Go Test Mode
By keying Installer code + [#] + [4], a mode similar to the test mode is entered, but the wireless receiver gain is reduced. Checking in
this mode not only assists in determining good mounting locations for the transmitters when the system is being installed, but also
verifies that the RF transmission has sufficient signal amplitude margin for the installed system.
1. Enter
the
Installer code + [#] + [4].
2.
Once transmitters are placed in their desired locations and the approximate length of wire to be run to sensors is connected to the
transmitter's screw terminals, fault each transmitter. Do not conduct this test with your hand wrapped around the transmitter, as
this will cause inaccurate results.
•
The keypad will beep three times to indicate signal reception.
•
If the keypad does not beep, reorient or move the transmitter to another location. Usually a few inches in either direction is all
that is required.
3.
Exit the Go/NoGo mode by keying Installer code + OFF [1] key.
Automatic Standby Battery Tests
An automatic test is conducted every 4 minutes to ensure that a standby battery is present and properly connected. If a battery is not
present or is not properly connected, a SYSTEM LO BAT message is displayed and, if so programmed, is reported to the central station.
A battery capacity test is automatically conducted for 2 minutes every 6 hours, beginning 6 hours after exiting the Programming mode
or after powering up the system. In addition, entry into the Test mode will also cause a battery capacity test to be initiated. If the
battery cannot sustain a load, a SYSTEM LO BAT message is displayed and, if programmed to do so, sends a report to the central
station.
Trouble Conditions
The word CHECK on the keypad's display, accompanied by a rapid beeping at the keypad, indicates that there is a trouble condition in
the system. The audible warning sound can be silenced by pressing any key.
Instruct users to call for service immediately upon seeing any of the following messages:
CHECK and BATTERY Displays
•
A display of CHECK and one or more zone numbers indicates that a problem exists with the displayed zone(s) and requires
attention.
•
A display of CHECK and 09 indicates that communication between control and a zone expander or wireless receiver is
interrupted. Check the wiring and DIP switch settings on the units. Also see CHECK 70 and CHECK 90 below.
•
If there are wireless sensors in the system, the CHECK condition may also be caused by some change in the environment that
prevents the receiver from receiving signals from a particular sensor.
•
A display of BAT (on fixed-word keypads) or SYSTEM LO BAT (on alpha keypads) with no zone number indicates that the
system's main standby battery is weak.
•
A display of BAT (on fixed-word keypads) or LO BAT (on alpha keypads) with a zone number and a once per minute "beeping" at
the keypad indicates that a low battery condition exists in the wireless sensor displayed (zone "00" indicates a wireless keypad). If
the battery is not replaced within 30 days, a CHECK display may occur.
•
Bell Failure (CHECK 70) Wiring loop to external sounder is either open or shorted.
•
RCVR Jam (CHECK 90) RF jam detected.
•
NOTE: Some wireless sensors contain a nonreplaceable long-life battery that requires replacement of the entire unit at the end
of battery life (e.g., 5802, 5802CP).
Power Problems
•
If the keypad display is blank, and the POWER indicator (if present) is not lit, primary AC power for the system has been
interrupted. In this case, the backup battery is also missing or totally discharged, the system will remain inoperative until AC
power and/or battery backup power is restored to normal.
NOTE: The control panel always powers up in its previous state (armed or disarmed) after a complete power failure, but will
not retain any memory of bypasses.
•
If the message AC LOSS (on alpha keypads) or NO AC (on fixed-word keypads) is displayed, and the POWER indicator (if
present) is off, the keypad is operating on battery power only.
NOTE: There is a random delay of up to 30 minutes before the system will report an AC failure to the central station. The
keypad response is about 6 seconds. The Restore Report has a random delay of up to 30 minutes (if the AC Failure Report was
sent).
•
If the battery standby capacity is used up during a prolonged AC power outage, the control's auxiliary power will shut down to
minimize deep discharge of the battery.
Содержание VISTA-10ES
Страница 24: ...VISTA 10SE Installation and Setup Guide 3 4...
Страница 34: ...VISTA 10SE Installation and Setup Guide 4 10...
Страница 44: ...VISTA 10SE Installation and Setup Guide 5 10...
Страница 58: ...VISTA 10SE Installation and Setup Guide 9 4...
Страница 66: ...VISTA 10SE Installation and Setup Guide 11 6...
Страница 68: ...VISTA 10SE Installation and Setup Guide 12 2...
Страница 80: ...1 9 l N7227V6 7 01 165 Eileen Way Syosset New York 11791 Copyright 2001 PITTWAY CORPORATION...