ADG-320 / ADG-330, 1Ø Motor
ADS-320 / ADS-330, 1Ø Motor
ELECTRICAL SERVICE SPECIFICATIONS (PER DRYER)
IMPORTANT:
NOTES:
A.
B.
C.
208 VAC AND 230/240 VAC ARE NOT THE SAME. When ordering,
specify exact voltage.
When fuses are used they must be dual element, time delay, current
limiting, class RK1 or RK5 ONLY. Calculate/determine correct fuse
value, by applying either local and/or National Electrical Codes to
listed appliance amp draw data.
Circuit breakers are thermal-magnetic (industrial) motor curve type
ONLY. For others, calculate/verify correct breaker size according to
appliance amp draw rating and type of breaker used.
Circuit breakers for 3-phase (3ø) dryers must be 3-pole type.
SERVICE
VOLTAGE
PHASE
WIRE
SERVICE
APPROX.
AMP DRAW
CIRCUIT
BREAKER
60 Hz
50 Hz
120
1ø
2
7.8
—
15
208
1ø
2
4.8
—
15
220
1ø
2
5.3
4.3
15
230
1ø
2
5.1
4.3
15
240
1ø
2
4.4
4.3
15
3. Grounding
A ground (earth) connection
must be
provided and installed in accordance with state and local codes. In the
absence of these codes, grounding
must conform
to applicable requirements of the National Electrical Code
ANSI/NFPA NO. 70-LATEST EDITION, or in Canada, the installation
must conform
to applicable Canada
Standards: Canadian Electrical Codes Parts 1 & 2 CSA C22.1-1990 or LATEST EDITION. The ground
connection may be to a proven earth ground at the location service panel.
For added personal safety, when possible, it is suggested that a separate ground wire (sized per local codes) be
connected from the ground connection of the dryer to a grounded cold water pipe.
DO NOT ground to a gas
pipe or hot water pipe
. The grounded cold water pipe must have metal to metal connections
ALL
the way to the
electrical ground. If there are any nonmetallic interruptions, such as, a meter, pump, plastic, rubber, or other
insulating connectors, they
must be
jumped out with no. 4 wire and securely clamped to bare metal at both
ends.
IMPORTANT:
For personal safety and proper operation, the dryer
must be
grounded.
4. Electrical Service Specifications (per pocket)
IMPORTANT:
The dryer
must be
connected to the electrical supply shown on the dryer data label
located on the inside of the middle access (control) door.
WARNING:
Any damage done to dryer components due to improper voltage application or
connections will automatically VOID THE WARRANTY.
Check your national and local code for breaker and wire size
7/9/14
NOTE:
Contact factory for electrical information not listed.