background image

Operator’s Guide for Rugged-UPS

TM 

1252 Series 

 

91-0120 Rev. B                                                     21 

  © Acumentrics Corporation 2007-2008 

 

The ACG1UBP provides 22 minutes of additional runtime typical (for a total of 26 minutes at 
full load typical). 

 

The ACG1UBP-C2 provides 14 minutes of additional runtime (for a total of 18 minutes at full 
load). 

 

To operate with either model, connect the male end of the cable to the connector on the back panel of 
the UPS.  Connect the female end to the connector on the ACG1UBP.  This operation may be done 
either when the unit is shut down (prior to power up), or when the unit is operating. 

 
 

The 

ACG1252XRBP

 also has an internal fuse.  The connector pins are not energized until connected 

to the Rugged-UPS

TM

 1252.  The UPS cannot “cold start” with only the ACG1252XRBP – the UPS’s 

internal battery pack or AC input power / optional external DC input must be present for added safety.     

 

 

The ACG1252XRBP provides 15 minutes (typical) of additional runtime (for a total of 19 
minutes at full load,  typical). 

 
To operate the ACG1252XRBP, connect the male end of the cable to the connector on the back 
panel of the UPS.  Connect the female end to the connector on the XRBP.  This operation may be 
done either when the unit is shut down (prior to power up), or when the unit is operating. 
 

               

 

Operation 

The UPS operates on AC external input power. In case of AC power failure, the DC input (if present) is 
used as backup.  If the DC power fails the internal battery pack is used as backup.  The UPS only 
operates on its internal batteries if AC external power source is unavailable and DC power is unavailable.  
The internal battery pack allows for short term power backup in case of loss of external power which 
allows the user to shut down the system being powered in an orderly manner. 

Since operating without a battery pack will NOT supply any backup power if the primary power sources 
should fail, careful consideration should be taken when operating the device without a battery pack and 
connected to a viable external AC power source.  This means the system being powered could not be 
properly shutdown in the event of primary power failure. 

The following are optional functions which may be performed while using the UPS. 

Reset the Circuit Breaker 

To reset the AC circuit breaker after it has tripped, first move the circuit breaker switch handle fully to OFF 
and then move it to the ON position. If the circuit breaker trips repeatedly, refer to the troubleshooting 
procedures. 

NOTE:

 Do NOT hold the AC circuit breaker in the ON position. 

Battery Status 

To verify the battery pack is fully charged to its present capacity simply disconnect ALL external power 
except the battery and visually check the Battery Status Indicators on the front panel.  If ALL five 
indicators are ON, the battery pack is fully charged to its present capacity.  

Note:

  If any power (other 

than the battery) is being supplied to the unit, ALL the Battery Status Indicators may be illuminated which 
does NOT indicate the actual capacity left in the battery.  

Audible Alarm 

The audible alarm sounds in a variety of ways to indicate different alarms symptoms.  These alarms are 
associated with various status indicators. 

Refer to the list below

Alarm 

Indicators 

Cause 

Two (2) beeps every 15 seconds 

Internal DC indicator illuminated. 

Output power is being supplied by 

Содержание Rugged-UPS 1252 Series

Страница 1: ...Operator s Guide for Rugged UPSTM 1252 Series 91 0120 Rev B 1 Acumentrics Corporation 2007 2008 1252 Rugged UPS Series...

Страница 2: ...ne if additional product information updates are available The latest revision of the manual is also available at www acumentrics com Rugged UPS is a registered trademark of Acumentrics Corporation Co...

Страница 3: ...Panel Rugged UPS 14 Rugged UPS Series Model Numbers and Options 14 Acumentrics Part Numbering System 14 Setup 15 SNMP Capability and Operation 15 Start Up 20 Extended Run Modules 20 Operation 21 Reset...

Страница 4: ...Operator s Guide for Rugged UPSTM 1252 Series 91 0120 Rev B 4 Acumentrics Corporation 2007 2008 Inspection 29 Cleaning 29 Troubleshooting Procedures 29 END 31...

Страница 5: ...ile sealing electronic components from the damaging effects of moisture airborne particles and other contaminates in the operating environment The Rugged UPS 1252 is an ON LINE Power Factor Corrected...

Страница 6: ...s Do NOT obstruct the air intake in the front of the unit or the exhaust outlet at the rear of the Rugged UPS 1252 Sufficient airflow through the Rugged UPS is vital to its operation This UPS has an i...

Страница 7: ...for AC Input optional DC Input AC Output optional DC Output with Battery Pack ACG1252R 18B Features options that are present in this manual that do NOT correspond with your device should be disregarde...

Страница 8: ...nearby personnel ATTENTION Refer to the Operator s Guide for more information This symbol is intended to alert the user to the presence of important operating and maintenance instructions accompanying...

Страница 9: ...ance and packaging the equipment securely to avoid shipping damage using the original packaging If this packaging is no longer available Buyer shall contact the Customer Service Department for instruc...

Страница 10: ...ecifications Continuous Output Power 1250 VA 1000W AC Output Voltage 115 VAC 5 AC Output Frequency 60Hz 5 AC Output Waveform Sinusoidal Total Harmonic Distortion 1 5 with resistive load Environmental...

Страница 11: ...diagnostic tests whenever the product is initially turned ON and periodically during operation During operation the Overtemp and or Overload indicators will illuminate if a fault is detected If this o...

Страница 12: ...for at least 5 seconds to supply power to the Rugged UPS and enable the audible alarms Briefly hold the switch in the OFF position to turn the Rugged UPS off To disable the audible alarm briefly hold...

Страница 13: ...tion to indicate the operating point is close to tolerance This indicator is NOT illuminated when the AC source drops below 80 VAC causing the Rugged UPS to switch to external DC If external DC is una...

Страница 14: ...nector used by the manufacturer to program units The AC Input Breaker will trip when the current exceeds the UPS s capacity Refer to the Rear Panel photo and callouts below Rugged UPS Series Model Num...

Страница 15: ...of a 10 100 Base T network interface using a standard RJ45 connector SNMP v3 protocol is supported with DHCP enabled The interface card has its own MAC address which is included with the documentatio...

Страница 16: ...mentations Read upsObjects 1 upsIdent 1 upsIdentName 5 String A string identifying the UPS Read upsObjects 1 upsIdent 1 upsIdentAttachedDevices 6 String A string identifying the devices attached to th...

Страница 17: ...ry voltage Read upsObjects 1 upsBattery 2 upsBatteryTemperature 7 int The ambient temperature at or near the UPS Battery casing Read upsObjects 1 upsInput 3 upsInputLineBads 1 int A count of the numbe...

Страница 18: ...psAlarmTable 2 upsAlarmEntry 1 upsAlarmTime 3 Stamp The value of sysUpTime when the alarm condition was detected If the alarm condition was detected at the time of agent startup and presumably existed...

Страница 19: ...wer is lost Read upsObjects 1 upsAlarm 6 upsWellKnownAlarms 3 upsAlarmTempBad 5 OID A temperature is out of tolerance Read upsObjects 1 upsAlarm 6 upsWellKnownAlarms 3 upsAlarmInputBad 6 OID An input...

Страница 20: ...are absolutely necessary The On Internal DC indicator will be illuminated Monitor the battery status via the Battery Status indicators Indicators identify the present capacity of the battery pack and...

Страница 21: ...ower is unavailable The internal battery pack allows for short term power backup in case of loss of external power which allows the user to shut down the system being powered in an orderly manner Sinc...

Страница 22: ...aterials from storage and repackage the equipment reversing the sequence of instructions used for unpacking Follow standard shipping procedures for your organization Operation under extreme heat In ho...

Страница 23: ...e unit and are opto isolated and driven by RS 232 transceivers The simple signal mode allows remote turn on off by the user supplying logic high true levels to the pins listed in table 1 This can be a...

Страница 24: ...urned Please note that the commands are case sensitive The first command you must enter to start is G this puts the unit into smart mode You will also need the following information Baud rate 2400 Dat...

Страница 25: ...gged UPSTM 1252 Series 91 0120 Rev B 25 Acumentrics Corporation 2007 2008 Legend Signifies Pin Signifies Pin socket AC Input Pin Out Functionality Plug Part Number MS3476W14 4S A B D C To line To Grou...

Страница 26: ...oration 2007 2008 AC Output Pin Out Functionality Warning DO NOT USE THIS CABLE IN A 230VAC APPLICATION Plug Part Number MS3476W14 4P Optional DC Input Pin Out Functionality Plug Part Number CA3102E20...

Страница 27: ...on 2007 2008 Optional DC Output Pin Out Functionality Plug Part Number MS3476L14 04P Optional Extended Run Pin Out Functionality Plug Part Number CA3102E20 14SBF80 A D B C Not Used Not Used Black Nega...

Страница 28: ...Supplementary Recharge Intervals Storage Temperature Recharge Interval Below 20 C 68 F Every six months Between 20 C and 30 C 68 F and 86 F Every three months Over 30 C 86 F Storage to be avoided The...

Страница 29: ...e g paper towels on the device Troubleshooting Procedures The following paragraphs explain the Troubleshooting Procedures used in this Section and list all unit level troubleshooting categories and ar...

Страница 30: ...erloading UPS Flip the Main Power Switch to the ON position 6 Audible alarm continuously sounds with the Overtemp indicator illuminated UPS internal heat sink temperature is critically high Ensure UPS...

Страница 31: ...Operator s Guide for Rugged UPSTM 1252 Series 91 0120 Rev B 31 Acumentrics Corporation 2007 2008 END...

Отзывы: