background image

Operator’s Guide for Rugged-UPS

TM 

1252 Series 

 
 
 

91-0120 Rev. B                 20 

 

© Acumentrics Corporation 2007-2008                         

Start-Up 

Normal Start-up is starting with external AC and /or DC Power available to the UPS. 

 

Verify  the  UPS  is  properly  connected  and  that  external  AC  and/or  DC  power  is  applied  to  the 
UPS. 

 

Verify the ground cable is attached. 

 

Turn the AC Circuit Breaker switch to ON. 

 

Hold  the  ON/OFF  switch  in  the  ON  position  for  up  to  5  seconds  and  then  release  the  switch.   

NOTE:    If  the  electronics  (e.g.  capacitors)  are  fully  discharged,  failure  to  follow  this  step  will 
create a false failure. 

 

After 10 seconds has elapsed, verify the following indicators illuminate: 

  Battery Status indicators are illuminated identifying a battery is present and appropriate charge 

status when the device is operating on battery only.   

  AC Line indicator will illuminate when AC source is present. 

  DC Line indicator will illuminate when DC source is present. 

  Load indicators are illuminated. 

Start-up  on Internal  Battery  Pack (cold starting):  when NO External power is available, the UPS can be 
started  using  its  internal  battery  pack.  If  the  battery  pack  is  fully  charged,  the  UPS  will  operate  up  to  4 
minutes at full load typical. 

 

Hold the ON/OFF switch in the ON position for approximately 1 – 5 seconds and then release the 
switch. 

 

To prolong the battery charge, turn on only those loads which are absolutely necessary. 

 

The “On Internal DC” indicator will be illuminated.  Monitor the battery status via the Battery 
Status indicators.  Indicators identify the present capacity of the battery pack and the audible 
alarm beeps twice every fifteen (15) seconds.  As the charge on the battery pack depletes, the 
battery status indicators will extinguish.  An audible alarm will begin to sound every second with 
the second to last indicator blinking and will continue until the last indicator is blinking indicating 
the battery pack is nearly depleted and low-battery shutdown is imminent.  

NOTE:  To minimize the risk of arching on the battery connectors please be sure when inserting 
or removing the battery pack that the unit has AC input connected.  

NOTE:

 

The  battery  indicators  identify  the  charge  status  of  the  battery  when  operating  on 
battery ONLY. The battery capacity diminishes over time. 

Extended Run 
Modules 

The Rugged-UPS

TM

 1252 has optional extended run capability, using either the ACG1252XRBP (2U 

high) or the ACG1UBP (1U high).  Both modules are shipped with an extended run battery cable, 
appropriate for the model being used.   
 
There are two versions of the 

ACG1UBP

.  Both have an internal fuse.  The connector pins are not 

energized until connected to the Rugged-UPS

TM

 1252.  The UPS cannot “cold start” with only the 1U 

Extended Run Battery Pack – the UPS’s internal battery pack or AC input power / optional DC input 
power must be present for added safety.  The LED Panel Indicator is illuminated when the unit is 
charging / discharging, or when in stand-by mode.   

 

Содержание Rugged-UPS 1252 Series

Страница 1: ...Operator s Guide for Rugged UPSTM 1252 Series 91 0120 Rev B 1 Acumentrics Corporation 2007 2008 1252 Rugged UPS Series...

Страница 2: ...ne if additional product information updates are available The latest revision of the manual is also available at www acumentrics com Rugged UPS is a registered trademark of Acumentrics Corporation Co...

Страница 3: ...Panel Rugged UPS 14 Rugged UPS Series Model Numbers and Options 14 Acumentrics Part Numbering System 14 Setup 15 SNMP Capability and Operation 15 Start Up 20 Extended Run Modules 20 Operation 21 Reset...

Страница 4: ...Operator s Guide for Rugged UPSTM 1252 Series 91 0120 Rev B 4 Acumentrics Corporation 2007 2008 Inspection 29 Cleaning 29 Troubleshooting Procedures 29 END 31...

Страница 5: ...ile sealing electronic components from the damaging effects of moisture airborne particles and other contaminates in the operating environment The Rugged UPS 1252 is an ON LINE Power Factor Corrected...

Страница 6: ...s Do NOT obstruct the air intake in the front of the unit or the exhaust outlet at the rear of the Rugged UPS 1252 Sufficient airflow through the Rugged UPS is vital to its operation This UPS has an i...

Страница 7: ...for AC Input optional DC Input AC Output optional DC Output with Battery Pack ACG1252R 18B Features options that are present in this manual that do NOT correspond with your device should be disregarde...

Страница 8: ...nearby personnel ATTENTION Refer to the Operator s Guide for more information This symbol is intended to alert the user to the presence of important operating and maintenance instructions accompanying...

Страница 9: ...ance and packaging the equipment securely to avoid shipping damage using the original packaging If this packaging is no longer available Buyer shall contact the Customer Service Department for instruc...

Страница 10: ...ecifications Continuous Output Power 1250 VA 1000W AC Output Voltage 115 VAC 5 AC Output Frequency 60Hz 5 AC Output Waveform Sinusoidal Total Harmonic Distortion 1 5 with resistive load Environmental...

Страница 11: ...diagnostic tests whenever the product is initially turned ON and periodically during operation During operation the Overtemp and or Overload indicators will illuminate if a fault is detected If this o...

Страница 12: ...for at least 5 seconds to supply power to the Rugged UPS and enable the audible alarms Briefly hold the switch in the OFF position to turn the Rugged UPS off To disable the audible alarm briefly hold...

Страница 13: ...tion to indicate the operating point is close to tolerance This indicator is NOT illuminated when the AC source drops below 80 VAC causing the Rugged UPS to switch to external DC If external DC is una...

Страница 14: ...nector used by the manufacturer to program units The AC Input Breaker will trip when the current exceeds the UPS s capacity Refer to the Rear Panel photo and callouts below Rugged UPS Series Model Num...

Страница 15: ...of a 10 100 Base T network interface using a standard RJ45 connector SNMP v3 protocol is supported with DHCP enabled The interface card has its own MAC address which is included with the documentatio...

Страница 16: ...mentations Read upsObjects 1 upsIdent 1 upsIdentName 5 String A string identifying the UPS Read upsObjects 1 upsIdent 1 upsIdentAttachedDevices 6 String A string identifying the devices attached to th...

Страница 17: ...ry voltage Read upsObjects 1 upsBattery 2 upsBatteryTemperature 7 int The ambient temperature at or near the UPS Battery casing Read upsObjects 1 upsInput 3 upsInputLineBads 1 int A count of the numbe...

Страница 18: ...psAlarmTable 2 upsAlarmEntry 1 upsAlarmTime 3 Stamp The value of sysUpTime when the alarm condition was detected If the alarm condition was detected at the time of agent startup and presumably existed...

Страница 19: ...wer is lost Read upsObjects 1 upsAlarm 6 upsWellKnownAlarms 3 upsAlarmTempBad 5 OID A temperature is out of tolerance Read upsObjects 1 upsAlarm 6 upsWellKnownAlarms 3 upsAlarmInputBad 6 OID An input...

Страница 20: ...are absolutely necessary The On Internal DC indicator will be illuminated Monitor the battery status via the Battery Status indicators Indicators identify the present capacity of the battery pack and...

Страница 21: ...ower is unavailable The internal battery pack allows for short term power backup in case of loss of external power which allows the user to shut down the system being powered in an orderly manner Sinc...

Страница 22: ...aterials from storage and repackage the equipment reversing the sequence of instructions used for unpacking Follow standard shipping procedures for your organization Operation under extreme heat In ho...

Страница 23: ...e unit and are opto isolated and driven by RS 232 transceivers The simple signal mode allows remote turn on off by the user supplying logic high true levels to the pins listed in table 1 This can be a...

Страница 24: ...urned Please note that the commands are case sensitive The first command you must enter to start is G this puts the unit into smart mode You will also need the following information Baud rate 2400 Dat...

Страница 25: ...gged UPSTM 1252 Series 91 0120 Rev B 25 Acumentrics Corporation 2007 2008 Legend Signifies Pin Signifies Pin socket AC Input Pin Out Functionality Plug Part Number MS3476W14 4S A B D C To line To Grou...

Страница 26: ...oration 2007 2008 AC Output Pin Out Functionality Warning DO NOT USE THIS CABLE IN A 230VAC APPLICATION Plug Part Number MS3476W14 4P Optional DC Input Pin Out Functionality Plug Part Number CA3102E20...

Страница 27: ...on 2007 2008 Optional DC Output Pin Out Functionality Plug Part Number MS3476L14 04P Optional Extended Run Pin Out Functionality Plug Part Number CA3102E20 14SBF80 A D B C Not Used Not Used Black Nega...

Страница 28: ...Supplementary Recharge Intervals Storage Temperature Recharge Interval Below 20 C 68 F Every six months Between 20 C and 30 C 68 F and 86 F Every three months Over 30 C 86 F Storage to be avoided The...

Страница 29: ...e g paper towels on the device Troubleshooting Procedures The following paragraphs explain the Troubleshooting Procedures used in this Section and list all unit level troubleshooting categories and ar...

Страница 30: ...erloading UPS Flip the Main Power Switch to the ON position 6 Audible alarm continuously sounds with the Overtemp indicator illuminated UPS internal heat sink temperature is critically high Ensure UPS...

Страница 31: ...Operator s Guide for Rugged UPSTM 1252 Series 91 0120 Rev B 31 Acumentrics Corporation 2007 2008 END...

Отзывы: