Operator’s Guide for Rugged-UPS
TM
1252 Series
91-0120 Rev. B 19
© Acumentrics Corporation 2007-2008
UpsTrapAlarmEntry
upsTraps(2)
Added(3)
Trap
This trap is sent each time an alarm is
inserted intoto the alarm table. It is
sent on the insertion of all alarms
except for upsAlarmOnBattery and
upsAlarmTestInProgress.
Read
UpsTrapAlarmEntry
upsTraps(2)
Removed(4)
Trap
This trap is sent each time an alarm is
removed fromthe alarm table. It is
sent on the removal of allalarms
except for upsAlarmTestInProgress.
Read
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
upsAlarmOnBattery(2)
OID
The UPS is drawing power from the
batteries.
Read
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
upsAlarmLowBattery(3)
OID
The remaining battery run-time is less
than or equal to
upsConfigLowBattTime.
Read
UpsAlarmDepleted
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
Battery(4)
OID
The UPS will be unable to sustain the
present load when and if the utility
power is lost.
Read
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
upsAlarmTempBad(5)
OID
A temperature is out of tolerance.
Read
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
upsAlarmInputBad(6)
OID
An input condition is out of tolerance.
Read
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
upsAlarmOutputBad(7)
OID
An output condition (other than
OutputOverload) isout of tolerance.
Read
UpsAlarmOutput
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
Overload(8)
OID
The output load exceeds the UPS
output capacity.
Read
UpsAlarmOutputOff
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
AsRequested(11)
OID
The UPS has shutdown as requested,
i.e., the output is off.
Read
UpsAlarmUpsOff
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
AsRequested(12)
OID
The entire UPS has shutdown as
commanded.
Read
UpsAlarmUpsOutput
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
Off(14)
OID
The output of the UPS is in the off
state.
Read
UpsAlarmUpsSystem
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
Off(15)
OID
The UPS system is in the off state.
Read
upsObjects(1).upsAlarm(6).upsWellKnownAlarms(3)
upsAlarmGeneralFault(18)
OID
A general fault in the UPS has been
detected.
Read