Operator’s Guide for Rugged-UPS
TM
1252 Series
91-0120 Rev. B 16
© Acumentrics Corporation 2007-2008
MIB/Instance
Variable
Type
Description
Value
Range
Access
upsObjects(1).upsIdent(1)
upsIdentManufacturer(1)
String
The name of the UPS manufacturer.
Read
upsObjects(1).upsIdent(1)
upsIdentModel(2)
String
The UPS Model designation.
Read
UpsIdentUPSSoftware
upsObjects(1).upsIdent(1)
Version(3)
String
The UPS firmware/software
version(s). This variable may or may
not have the same value as
upsIdentAgentSoftwareVersion in
some implementations.
Read
UpsIdentAgentSoftware
upsObjects(1).upsIdent(1)
Version(4)
String
The UPS agent software version.
This variable may or may not have the
same value as
upsIdentUPSSoftwareVersion in
some implementations.
Read
upsObjects(1).upsIdent(1)
upsIdentName(5)
String
A string identifying the UPS. .
Read
upsObjects(1).upsIdent(1)
upsIdentAttachedDevices(6)
String
A string identifying the devices
attached to the output(s) of the UPS.
This object should be set by the
administrator.
Write
1:unknown
2:Normal
battery
3:Low
battery
4:Depleted
upsObjects(1).upsBattery(2
upsBatteryStatus(1)
int
The indication of the capacity
remaining in the UPS system's
batteries. A value of battery Normal
indicates that the remaining run-time
is greater than
upsConfigLowBattTime. A value of
batteryLow indicates that the
remaining battery run-time is less than
or equal to upsConfigLowBattTime. A
value of batteryDepleted indicates
that the UPS will be unable to sustain
the present load when and if the utility
power is lost (including the possibility
that the utility power is currently
absent and the UPS is unable to
sustain the output).
battery
Read