User Manual 

 

 

E200 Series UPS 

 

 

E201(E) 

 

E202(E) 

 

E203(E)

 

 

 

Summary of Contents for E201

Page 1: ...Road Eastfield Industrial Estate Scarborough North Yorkshire YO11 3DU UK info dalepowersolutions com www dalepowersolutions com 44 0 1723 583511 S5264FU01 Rev 3 Dale Power Solutions Ltd User Manual E200 Series UPS E201 E E202 E E203 E ...

Page 2: ...h may not be copied reproduced or disclosed to a third party without written permission Dale Power Solutions Ltd reserves the right to make changes in specification without notice or liability All information is subject to Dale Power Solutions Ltd own data and is considered accurate at time of publishing ...

Page 3: ...el layout 9 Unpacking the UPS 10 Wiring the UPS 10 Operation 11 Working modes 11 On Line mode 11 Bypass mode 11 Battery mode 11 ECO mode 11 Front panel controls and indicators 12 LCD display 13 Before switch on 13 Switching on the UPS 13 Switching off the UPS 14 Self test 14 Mute sounds 14 Settings 14 ECO mode 15 Bypass mode 15 Output voltage level 16 Checking parameters 17 Fault mode 18 Maintenan...

Page 4: ...RS232 serial port 21 USB port 21 SNMP card advanced monitoring and control 21 Relay card advanced monitoring and control 22 Appendix 2 Specifications 24 Electrical 24 Environment 25 Mechanical 25 Appendix 3 Optional equipment 26 Appendix 4 Fault codes 26 Appendix 5 LED indicator status 27 ...

Page 5: ...eable parts There are high capacity batteries inside and other electronics that can cause electric shock If the UPS requires internal maintenance or battery replacement contact Dale Power Solutions The UPS must be switched off prior to removal of the AC mains input plug from the UPS or the mains supply socket as detailed on the warning label fitted on the UPS The UPS mains input cable must be conn...

Page 6: ...res auto control systems and telecommunication systems Product range The following table lists the models available in the E200 series Models with an E suffix are designed for operation with an external battery Capacity 1 kVA 2 kVA 3 kVA Model E201 E201E E202 E202E E203 E203E Battery location Internal External Internal External Internal External Battery voltage 24 V 48 V 72 V No of 12 V batteries ...

Page 7: ...with power factor correction High frequency double conversion and a wide input voltage range ensure continuous output for areas with poor power supply regulation DSP technology for digital control ensures high reliability circuit protection and self diagnostics in the unlikely event of a fault Intelligent digital battery management extends battery life and ensures optimum performance An LCD panel ...

Page 8: ...male connectors for input and output respectively If using external batteries you will be supplied with a separate battery box that includes a battery breaker or you may be supplied with a set of battery leads and a breaker 50 A MCB single pole Caution As a minimum you must fit a 50 A single pole MCB in the battery line However you can use a double pole breaker if you prefer If supplying your own ...

Page 9: ...Rear panel layout Figure 2 and Figure 3 show the rear panel connections for the two sizes of UPS Figure 2 Rear panel layout 1 kVA unit Figure 3 Rear panel layout 2 3 kVA units Surgeprotected networkconnection Surgeprotected networkconnection ...

Page 10: ...nals card if fitted Do not use a pozidrive PZ screwdriver To connect the UPS to your system 1 If your system uses an external battery check that the number of 12 V blocks matches the number specified in your order a Before connecting the battery make sure that UPS is unplugged and the battery breaker is turned off b Plug the battery cable into the rear of the UPS see Figure 2 or Figure 3 2 Using t...

Page 11: ...S fails a serious fault has occurred within the UPS that must be repaired The UPS is turned off In bypass mode the inverter LED is off and the amber bypass LED is on Battery mode In battery mode the load is supplied from the battery via the DC DC converter and inverter the UPS beeps every 3 s and the AC DC converter and charger are turned off The UPS switches to battery mode when there is no a c i...

Page 12: ...at the UPS is working in bypass mode The buzzer beeps every 2 minutes When on with the green inverter LED indicates that the UPS working in ECO mode Indicates that the UPS is in battery mode Flashes under fault conditions Indicates that the UPS is turned on and the following conditions apply the a c input if present is within limits no overload battery connected The following table describes the b...

Page 13: ...hours as they may have lost charge during the time between production and installation To switch on the UPS Note If there is no mains and you want to start the UPS and run it from the battery ensure the mains input cable is connected and is correctly earthed then follow the procedure from step 3 1 If your installation has an external battery switch on the battery breaker 2 Switch on the mains to t...

Page 14: ...y Switching off the UPS Caution All power to the loads will be removed when you follow this procedure To switch off the UPS 1 On the front panel press and hold until a beep is heard after approximately half a second 2 Switch off the mains to the UPS Self test To perform a self test 1 Ensure bypass mode is turned off see Bypass mode on page 15 2 On the front panel press and hold for 1 s A self test...

Page 15: ... OFF stops flashing 4 Press or to display ON which flashes 5 Press for more than 0 5 s but less than 2 s ON stops flashing 6 Press for more than 2 s The green inverter and amber bypass LEDs should be on To turn off ECO mode Use the procedure above and select OFF instead of ON Bypass mode To enable switch to bypass mode 1 On the front panel press for more than 2 s 2 Press or until the following is ...

Page 16: ...ress for more than 2 s To disable switch to bypass mode Use the procedure above and select OFF instead of ON Output voltage level To change the output voltage Caution Before changing the output voltage turn off all loads and ensure they are rated for the new output voltage 1 On the front panel press for more than 2 s 2 Press or until the following is displayed 3 Press for more than 0 5 s but less ...

Page 17: ...0 V 230 V the default value and 240 V 6 Press for more than 0 5 s but less than 2 s The voltage stops flashing 7 Press for more than 2 s Checking parameters To check the UPS parameters Press or to display the parameter you wish to check If you press for more than 2 s the UPS cycles through the parameters three times automatically Examples are shown below Output Load Temperature Input Battery ...

Page 18: ...e UPS cuts off the output or switches to bypass mode and sounds the buzzer The warning LED is lit and the display shows a fault code A list of fault codes is shown on page 26 In this mode you can Mute the buzzer temporarily until the fault is corrected Turn off the UPS ...

Page 19: ...ows Maintain the ambient temperature in the range 15 to 25 C Avoid discharge currents of less than 10 of full load current Do not operate the UPS in battery mode continuously for more than the specified autonomy hold up time Charge the battery for at least 12 hours every 3 months if it has not been used If the ambient temperature is higher than 25 C charge the battery every 2 months Maintain exter...

Page 20: ...replace the battery Mains normal but UPS has no input UPS input breaker open circuit Reset the input breaker and then make sure there is a mains supply Back up time low Battery not fully charged Recharge the battery for at least 8 hours UPS overload Check loads and if necessary remove some loads Batteries worn out Contact distributor for replacement batteries UPS doesn t start up after pressing th...

Page 21: ... 3 RX 2 GND 5 GND 5 RS232 communication data format Parameter Value Baud rate 2400 bps Byte length 8bit End bit 1bit Parity check Null USB port The USB port is internally wired to the RS232 port through a converter and provides the same monitoring capabilities as above To enable USB control 1 Connect the UPS to your computer using the supplied USB cable Note This connection will override an RS232 ...

Page 22: ...scription Terminal block connection no DB9 pin no Additional information UPS failure N C 1 1 UPS failure N O 2 1 Bypass active N C 1 3 Bypass active N O 4 6 UPS summary alarm N C 1 5 UPS in battery mode Battery low UPS internal failure UPS summary alarm N O 6 2 Battery low N C 1 7 Battery low N O 8 7 UPS on N C 1 9 UPS on N O 10 8 Utility failure N C 1 11 Utility failure N O 12 9 Utility or mains ...

Page 23: ...he connection table on the previous page and the pin out information below To connect to the 16 way terminal block Note There is limited space between the terminal block and the edge of the mounting slot It is therefore advisable to use fine wire 0 5 mm2 max to make it easier to bend and dress the wires out of the way 1 Using a PH2 Phillips screwdriver remove the two screws holding the relay card ...

Page 24: ...free Backup time E201 E202 E203 4 mins Suffix E backup time is determined by the size of the external battery Charge current E201 E202 E203 1 A E201E E202E E203E 4 A Output Output type Single phase L N and E Rated voltage 208 220 230 240 V a c Power factor 0 7 Output precision 2 Voltage distortion THD 3 with 100 linear load 5 with 100 non linear load Frequency Line mode Battery mode 1 When input f...

Page 25: ...ironment Operating temperature 0 to 40C Storage temperature 25C to 55C Relative humidity 0 to 95 non condensing Altitude 1500 m full power Over 1500m reduce the rated power output by 1 for every 100m increase in height Mechanical Model E201 E E202 E E203 E Height mm 215 337 Width mm 144 191 Depth mm 361 428 Net weight gross weight E201 10 2 11 kg E201E 5 2 6 kg E202 19 5 21 1 kg E202E 9 5 11 1 kg ...

Page 26: ... Extension battery box Dry contact relay card SNMP card Battery MCB box Bypass panel Appendix 4 Fault codes Fault Fault code Bus Fault 00 19 Inverter Fault 20 39 Over Heat 40 44 Output short circuit 45 49 Overload 50 54 Output Relay Fault 55 59 Input NTC Fault 60 64 Auxiliary Power Fault 65 69 Input Fuse Fault 70 74 Others 99 ...

Page 27: ...r is closed Inverter mode Every 4 s Ensure the battery breaker is closed Power up or start Six times Ensure the battery connections are secure 6 Output overload protection Overload warning on line mode Every s Remove less important loads Overload in line mode protection Long beeps Remove less important loads Overload warning battery mode Every s Remove less important loads Overload battery protect...

Page 28: ...Dale Power Solutions Ltd Salter Road Eastfield Industrial Estate Scarborough North Yorkshire YO11 3DU UK info dalepowersolutions com www dalepowersolutions com 44 0 1723 583511 ...