background image

Liebert

® 

EXS

30kVA And 40kVA 

UPS

UPS User Manual

Summary of Contents for EXS 0030kTH 16FN01000

Page 1: ...Liebert EXS 30kVA And 40kVA UPSUPS User Manual...

Page 2: ......

Page 3: ...tact the nearest Vertiv local sales office or service center 2018 Copyright 2020 by Vertiv Tech Co Ltd All rights reserved The contents in this document are subject to change without notice Vertiv Tec...

Page 4: ...be stored or remain de energized for a long period it must be placed in a dry and clean environment within specified temperature range 2 This product should be used in an appropriate operating environ...

Page 5: ...th connection is critical before connecting the input supply including both mains supply and battery 2 Earth leakage current is less than 2500mA 3 Transient and steady state earth leakage currents whi...

Page 6: ...The Manual Describes Following Equipment Product M odel 30kVA EXS 0030kTH16FN01000 40kVA EXS 0040kTH16FN01000...

Page 7: ...d Operating Modes 6 1 5 Battery Management 10 1 5 1 Normal Function 10 1 5 2 Advanced Function 11 1 5 3 Battery Temperature Compensation 12 1 6 Battery Protection 12 Chapter 2 Mechanical Installation...

Page 8: ...Changing Current Date And Time 60 5 12 Setting Password 61 Chapter 6 Parallel System And LBS System 64 6 1 General 64 6 2 Requirements 64 6 3 System Installation Procedures 64 6 3 1 Preliminary Check...

Page 9: ...l Characteristics Input Rectifier 94 10 5 Electrical Characteristics Battery 94 10 6 Electrical Characteristics Inverter Output 95 10 7 Electrical Characteristics Bypass Input 95 Appendix 1 LCD Parame...

Page 10: ...e reliability of power supply High input power factor wide input voltage range and output immune to grid interference thus adaptable to areas with unstable mains supply Full digital control platform a...

Page 11: ...matically and the system will transfer to battery output through inverter The length of the operation time in battery mode depends on the load and the battery capacity During this period if the batter...

Page 12: ...stem Up to four UPS modules can be parallel connected to form a parallel system to increase the system capacity and reliability The load is equally shared between the paralleled UPS modules Moreover t...

Page 13: ...cally transfer back to the normal mode without any manual intervention and the power to the load will not be interrupted In Battery mode the run indicator green is on alarm indicator yellow is on and...

Page 14: ...ure 1 7 Schematic diagram of ECO mode Note 1 In ECO mode if the bypass fails or the bypass voltage goes outside normal limits the UPS will transfer to Normal mode providing the output is not overloade...

Page 15: ...test in LCD Interval 30 360 days default setting 60 days The UPS also provides battery capacity self test function Periodically test the battery activity test the battery residual capacity judge the...

Page 16: ...AC distribution systems IEC60364 3 and must be of 3 phase 5 wire A B C N PE system W arning battery danger Take special care when installing batteries When connecting batteries the battery terminal g...

Page 17: ...Heat shrinkable tube Insulated torque wrench Torque screwdriver Multimeter Clip on ammeter 2 4 Unpacking Unpack the UPS and battery packages under the guidance of authorized service engineer Steps 1...

Page 18: ...adequate ventilation and should be located on concrete or other nonflammable and flat surfaces The ambient environment should be free of conductive powder such as metallic powder sulfide sulfur dioxi...

Page 19: ...ing 1 The lifting equipment for moving the UPS cabinet must have enough lift capacity Refer to Table 10 3 for its weight 2 Due to its intensity the castor may not be valid on the uneven surface 3 The...

Page 20: ...t cable differs with the UPS power ratings and input AC voltages provided that it meets the requirement of maximum input current including the maximum battery charge current see Table 3 1 UPS bypass a...

Page 21: ...ral guidance only If there are relevant local regulations the local regulations shall prevail 1 The cable size of the protective earth cable shall be selected according to the AC power failure level c...

Page 22: ...nfiguration Procedures 1 Dismantle the protective cover at rear of the cabinet 2 Remove the three shorting cables of common input configuration shown in Figure 3 1 Note to reinstall the bolts of power...

Page 23: ...as shown in Figure 3 3 Procedures 1 Open the cabinet front door remove the middle protective cover as shown in Figure 3 3 2 Wear arc protective gloves to connect battery input terminals N via the plas...

Page 24: ...t windows message and UPS alarm list 4 1 Introduction The operator and display panel is located on the front panel of the UPS The operator and display panel allows the user to operate and monitor the...

Page 25: ...parameters obtain information about the current UPS status and alarm messages as well as performing functional setting and control operations The LCD also stores historical alarm records that can be...

Page 26: ...ing pages Status page The Status page contains information about the Input Bypass Battery Output and Load See below Input Bypass Battery Output 220 0 50 00 381 2 220 2 220 8 50 00 50 00 381 9 381 7 L...

Page 27: ...35 Liebert EXS 30kVA And 40kVA UPS User Manual Log page The Log page can be used to access a list of current and historical UPS events See below About page The About page contains information about t...

Page 28: ...charge failed Condition is not met This prompt appears when you select the Freshening charge command while the battery freshening charge condition such as no battery charger failure is not met Turn on...

Page 29: ...m messages based on the Current and History menus Table 4 5 UPS alarm message list Alarm M eaning Input Phase Reversed The AC input phase rotation is reversed Input Voltage Abnormal The mains voltage...

Page 30: ...nce bypass mode Battery Voltage Low Battery voltage too low and out of the normal range based on the battery cells number setting Table 4 6 UPS fault message list Fault M eaning Input Backfeed Battery...

Page 31: ...ontact gives a command of charger shutdown then the charger will shut down Fault Clear Select the command of Clear faults via the Control page Silence Active Select the command of Mute Unmute audible...

Page 32: ...ECO Mode This alarm appears when input dry contact Suspend ECO Mode active The UPS will stay in inverter mode and ECO mode will be inhibitted Inhibit Trans to Inverter This alarm appears when input d...

Page 33: ...cables have been connected correctly and that the positive and negative battery poles are correct 3 Measure the mains voltage and frequency and verify that they are correct 4 The UPS output terminals...

Page 34: ...ge frequency and phase are correct and then back to the Flow page 6 Access the flow page press and hold the power button then the LCD prompt a dialogue box as shown in Figure 5 4 After selecting YES t...

Page 35: ...tead of the pure AC power from the inverter In Inverter mode press the power button If the bypass is normal the interface shown in Figure 5 6 will appear Select YES to transfer the UPS to Bypass mode...

Page 36: ...maintenance bypass switch Q3 At the moment the maintenance bypass parallels with the UPS bypass 4 Unplugging the EPO terminal disconnects the output switch Q5 main input switch Q1 and bypass input swi...

Page 37: ...aging coefficient battery capacity percentage when compared to a new battery 4 Stop the test If required the test may be stopped before completion by selecting Stop testing on the Command menu Note Th...

Page 38: ...ery terminals 5 8 UPS Reset Procedures After EPO After shutting down the UPS through EPO or reasons of inverter overtemperature overload battery overvoltage and DC bus voltage clear the fault accordin...

Page 39: ...ght the language see Figure 5 14 Figure 5 14 Language selection 4 Press the or key to select your required language then press the key to confirm it At this point the LCD information will be the displ...

Page 40: ...main menu screen 5 12 Setting Password 1 After switching the UPS on access the main menu screen and press the or key to move the cursor to select Settings See Figure 5 20 Figure 5 20 Main menu 2 Pres...

Page 41: ...nfirming new password 6 After confirming the new password press the key at this point a system prompt appears indicating that the password has been changed successfully see Figure 5 27 UPS address Car...

Page 42: ...el 6 3 2 Cabinet Installation Place the UPS modules side by side and interconnect as shown in Figure 6 1 The output distribution mode QE1 QE2 must be configured shown in Figure 6 1 is recommended to f...

Page 43: ...ower one is Normally Closed type 6 4 Operation Procedures For Parallel System 6 4 1 Check Before Start up 1 Check and confirm that the UPS power distribution mode is correct that the power cables and...

Page 44: ...UPS check whether there is an alarm on the LCD and confirm that the UPS parallel works normally c Follow the methods to start inverter of the third or the fourth UPS to connect the UPS into the paral...

Page 45: ...es are used to reintegrate a UPS module that has been previously isolated from the parallel system 1 If the UPS is equipped internal batteries make sure that the external battery terminals see Figure...

Page 46: ...UPS 1 UPS 4 Q5 Q1 Q2 Q3 Q5 cable To load STS Rectifier Parallel Rectifier Bypass Q1 Q2 Q3 UPS 1 UPS 4 Q5 Q1 Q2 Q3 Q5 cable Rectifier Parallel Figure 6 5 LBS system parallel system Note In a dual bus s...

Page 47: ...the intelligent cards on site Open the front door of the UPS you can see the protective cover located on the cabinet top Remove the protective cover to install communication device options including S...

Page 48: ...alled at Intellislot1 or Intellislot2 2 When installing the UNITY DP card or the UNITY LIFE card at Intellislot1 or Intellislot2 if you wish to change the baud rate just change the serial port 2 baudr...

Page 49: ...e Self check Stop Battery Maintenance Self check Alarm Cleared Pin13 and Pin15 shorted to enable this function Configurable input dry contact J13 13 15 GND_SELV 2 Inhibit_trans_ to_inverter On Generat...

Page 50: ...gure 7 7 Figure 7 7 REPO cable connection The cable connection procedures are as follows 1 Release the REPO port connection terminals 6 and 8 2 Strip the insulation from the ends of the two copper cor...

Page 51: ...firming that they blow air out of the ventilation holes on the rear panel 8 2 Battery Maintenance Note 1 Never invert the battery connections as this could result in fires 2 Never attempt to open batt...

Page 52: ...checking the UPS functions regularly Backup the load data before conducting the UPS functional check The procedures are as follows 1 Press the power button to check if the buzzer beeps the indicators...

Page 53: ...A Back up for 5min at full load Kit includes battery tray connection cables and battery separator EXS 0030kIBS10 30kVA Back up for 10min at 80 load Kit includes battery tray connection cables and batt...

Page 54: ...cation options and temperature sensor Name Type Description Appearance SIC card UF SNMP810 Remotely monitor UPS through TCP IP protocol and Internet Provide an extended net port cascade connect up to...

Page 55: ...selecting battery ground fault kit 7 Wall mounted installation hole 8 Protective door 9 Cabling hole for confirming the cable size and opening hole 10 Battery switch 9 6 2 Connection Of BCB Box Refer...

Page 56: ...IEC EN62040 2 Level 4 Surge protection Meets IEC EN62040 2 live line to earth withstand level 4 4kV withstand level 3 between live lines 2kV Safety IEC EN62040 1 SPD test Meets ANSI C62 41 live line t...

Page 57: ...ed power factor 1 Crest factor 3 1 Voltage harmonic distortion 1 5 linear load 4 5 non linear load Dynamic response recovery time ms 40 Frequency track rate Hz s Configurable range 0 1 0 6Hz s single...

Page 58: ...ECO inverter standby mode 50Hz Output Voltage Adjustment 208V 114 126V 220V 120 133V 380V 209 231V 400V 218 242V 415V 228 252V Note related to system voltage level 5 5 of nominal output voltage 120V 1...

Page 59: ...nverter General Purpose Dry Contact J13 1 I N A onGen Inhibit trans to inverter Ext_MIB Ext MBB status MOB Battery GND Fault Charger Off Suspend ECO mode Start Battery Maint Test Stop Battery Maint Te...

Page 60: ...applicable Insulation monitoring device when applicable This table is made following the regulation of SJ T 11364 Means the content of the hazardous substances in all the average quality materials of...

Page 61: ......

Page 62: ...eferred to are trade names trademarks or registered trademarks of their respective owners While every precaution has been taken to ensure accuracy and completeness herein Vertiv Co assumes no responsi...

Reviews: