214
System Manual SCK Gas Sampling System
42/23-81 EN Rev. 4
Errors and irregularities
If an error occurs, the system triggers automatic processes to protect the gas
sampling probe:
Phase Description
1
The sampling system is switched to manual mode.
2
The gas sampling probe is retracted out of the kiln.
WARNING!
Probe movement.
Do not stand in the area of travel of
the probe or probe carriage.
Result:
Because the gas sampling probe is in manual mode, the
gas sampling probe can no longer move in on its own.
Note:
In the event of danger to personnel, you can interrupt these automatic pro-
cesses by pressing the EMERGENCY-STOP switch.
The following table describes irregularities that may occur during operation of the
gas sampling system and measures to be taken to remedy them:
Observation Possible
causes
Measures
Untypical running
noise
Heat exchanger defec-
tive
Compressed-air
motor
defective
Inform internal mainte-
nance department or ABB
Service
Whistling noise
from compressed-
air system
Compressed-air
sys-
tem leak
See
Checking for leaks
on
page 171
Probe travel is jerky
Probe
carriage
rails
dirty
Wrong inclination of
probe carriage
Clean
rails
Readjust probe carriage
inclination using the ad-
justment screws, see
Probe retractor: Checking
and, if necessary, adjust-
ing the position of the
probe
on page 198
Probe not centered
in kiln aperture
Incorrect probe align-
ment/positioning
Realign
probe
Untypical or gur-
gling noises in the
cooling-water circuit
Air bubbles in the
cooling-water circuit
Vent
cooling-water
circuit,
see
Cooling module: Vent-
ing the cooling-water cir-
cuit
on page 206
Top up cooling water, see
Cooling module: Checking
and topping up cooling
water
on page 208
Unusual probe
movements (probe
rocks up and down,
sways to the sides,
jerky travel)
Loose
parts
Severe soiling of rails
Have trained experts find
out the cause
Automatic processes
Irregularities and
corrective action
Содержание SCK
Страница 2: ......
Страница 16: ......
Страница 36: ......
Страница 54: ......
Страница 110: ......
Страница 222: ......
Страница 232: ......
Страница 234: ...234 System Manual SCK Gas Sampling System 42 23 81 EN Rev 4 Pneumatic hydraulic interface plan ...
Страница 235: ...42 23 81 EN Rev 4 System Manual SCK Gas Sampling System 235 ...
Страница 236: ...236 System Manual SCK Gas Sampling System 42 23 81 EN Rev 4 Electrical connection plan ...
Страница 237: ...42 23 81 EN Rev 4 System Manual SCK Gas Sampling System 237 ...
Страница 238: ...238 System Manual SCK Gas Sampling System 42 23 81 EN Rev 4 Transformer connection plan ...
Страница 242: ......
Страница 243: ......