160
System Manual SCK Gas Sampling System
42/23-81 EN Rev. 4
How to put the system into maintenance mode:
Step Procedure
1
Make sure that no-one is standing in the area of probe retractor
travel.
2
On the control cabinet: Turn service switch
-S31
(1)
clockwise to
the
ON
position.
WARNING!
Actuating the service switch moves the probe out of the
kiln.
Do not stand in the area of travel of the probe or probe
carriage until the probe has reached its end position and the
warning lamps go out.
Result:
The gas sampling probe is automatically retracted out of
the kiln; the controller displays the
Maintenance
message.
3
Secure the service switch against unauthorized actuation.
4
When working on the retractor and gas sampling probe, additionally
actuate the EMERGENCY-STOP switch for reasons of safety.
5
Perform maintenance tasks.
6
Leave danger area around the retractor and close the protective
installation.
7
Turn service switch
-S31
counter-clockwise to the
OFF
position.
8
Re-insert the probe using the controller.
Path:
Operation
►
Probe
►
Probe Action
►
Insert
WARNING!
The probe moves into the kiln.
Do not stand in the
area of travel of the probe or probe carriage.
Instructions
Содержание SCK
Страница 2: ......
Страница 16: ......
Страница 36: ......
Страница 54: ......
Страница 110: ......
Страница 222: ......
Страница 232: ......
Страница 234: ...234 System Manual SCK Gas Sampling System 42 23 81 EN Rev 4 Pneumatic hydraulic interface plan ...
Страница 235: ...42 23 81 EN Rev 4 System Manual SCK Gas Sampling System 235 ...
Страница 236: ...236 System Manual SCK Gas Sampling System 42 23 81 EN Rev 4 Electrical connection plan ...
Страница 237: ...42 23 81 EN Rev 4 System Manual SCK Gas Sampling System 237 ...
Страница 238: ...238 System Manual SCK Gas Sampling System 42 23 81 EN Rev 4 Transformer connection plan ...
Страница 242: ......
Страница 243: ......