External accessories | 7 - Ekip Com Modbus TCP
143 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Remote configurations
Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter
Description
Default
Client/Server
Parameter for changing the configuration of the module from Server
Only to Client and Server and for integrating it into an interactive data
exchange network (see Ekip Com Hub on page 157)
IMPORTANT: if Client/Server, the module allows data
exchange like a normal Server function
Server only
IEEE 1588
enable
Allows the IEEE 1588 protocol for distribution of the clock and
synchronization signal to be enabled
(1)
.
OFF
Master IEEE
1588
Enables the module to be set up as a master in the the network
segment to which it belongs (synchronization clock).
OFF
IEEE 1588 delay
mechanism
Allows the data exchange mode between module and master, either
Peer-to-Peer or End-to-End, to be selected.
End-to-End
SNTP Client
enable
Allows the SNTP protocol for distribution of the clock and
synchronization signal to be enabled
(1)
OFF
Force Static IP
Address
Allows the network server that supplies the SNTP to be set.
0.0.0.0
Time zone
Defines the time zone to be used for synchronism
+00:00
Daylight Saving
Time
Used to select whether daylight saving time is present (ON) or not
(OFF) in the country to which the synchronization time refers
OFF
Disabilita
Gratuitos ARP
Permits (Enabled ARP) the periodic generation of a Gratuituos ARP
message, used by Ekip Connect to rapidly find the modules via
Ethernet scan without knowing the IP address beforehand
ARP Enabled
Access
protected by
password
Enables the writing operations performed via the network to be
protected by a password (Request password)
Standard mode
Password
Modbus TCP
With access protected by enabled password, this is the password to
use before each writing session
(2)
.
Local access
(1)
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
(2)
the parameter can only be changed via system bus in the remote configuration
Remote information
Additional information can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Information
Description
Boot and HW version
General module information
Flash CRC status e result Information about the correctness of the SW in the module
Stato Ekip Link
Signals Ethernet cable connection errors
SNTP Server Error
Error in communication with SNTP server
SNTP Server
Synchronisation
State of synchronism with SNTP server
IEEE 1588 status
Valid with Master IEEE 1588= ON, notifies the presence (Slave or PTP Master
Active) or absence (PTP Master but Passive) of the higher level master