 Plug-in Connection Unit Instruction Manual 

 

  Types: E125 S125 H125 L125

 

 

E250 S250 H250 L250 

 H160 

L160

 

 

 

 
 
 

 

 
 
 
 
 
 
 
 
 

 

 

This document has described the procedure which attaches Plug-in Connection unit in 

TemBreak2

 series.

 

 

Please retain this manual for future reference. The Manufacturer assumes no responsibility for 
damages resulting from non-application or incorrect application of the instructions provided herein.

 

 
 

7-2-10 Kamihigashi, Hiranoku, Osaka

 

547-0002, Japan

 

TEL:81-6-6791-9323/ FAX:81-6-6791-9274

 

Web Site: www.terasaki.co.jp

 

Email: [email protected]

 

 

2G0617SAA 

(KRB-5309)

 

 

2

Applicable Breaker Types/Packed Items

 

 

PC Unit

 

 

Items 

 

Applicable Breaker Types

 

Poles

 

Code No.

 

A B C D E F  G  H  I 

800009  6 1 - 4 6 -  1  2  - 

E125,S125 

4 800016 

8  - 1 4 8 -  1  4  - 

800023  6 1 - 4 - 6  1  2  - 

E250,S250 

4 800030 

8  - 1 4 - 8  1  4  - 

3 800061 

6  1 - 4 - 6  1  -  2 

H125,L125,H250,L250,H160,L160 

4 800078 

8  - 1 4 - 8  1  -  4 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

3

Assembly tools

 

  
 
 
 
 

 
 

1

Safety Notice

 

Be sure to read these Instructions and other associated documents accompanying the product 
thoroughly to be familiarize yourself with the product handling, safety information, and all other 
precautions before mounting, using, servicing, or inspecting the product. In these Instructions, 
safety notices are divided into 

Caution according to the hazard level: 

Caution : A caution notice with this symbol indicates that neglecting the suggested procedure     

or practice could result in moderate or slight personal injury and/or property damage. 

  Note that failing to observe 

Caution notices could result in serious injury/damage in some situations. 

Because safety notices contain important information, be sure to read and observe them.

 

Caution

 

Installation Precautions 

Clean the Plug-in Connection bolt mounting surface (contact surface with the breaker 

terminals). Otherwise, a fire may result. 

 

Insert the Plug-in Connection bolt the full depth until the mounting surface comes into 

contact with the breaker terminals, and tighten it with the PC bolt fixing screws. 

Otherwise, a fire may result. 

 

Tighten the Plug-in Connection bolt fixing screws and carrier fixing screws to the torque 

specified in this manual. Otherwise, a fire may result. 

 

Opration Precautions 

When the breaker trips open automatically, remove the cause; then close the breaker. 

Otherwise, a fire may result. 

 

Maintenance Precautions 

Service and/or inspection of the product must be done by persons having expert 

knowledge. 

 

Before service or inspection of this product, please ensure that no voltage is present on 

the breaker supply side. Any device upstream of this breaker should be suitably 

isolated otherwise electric shock may result. 

 

Regularly check that the Plug-in Connection bolt fixing screws are tightened to torque 

values shown within this manual, failure to do so may result in fire. 

 
 
 

D : 

φ

4

×

12

 

E : M6

×

16

 

F : M6

×

20

 

G

 

H : M4

×

55

 

B

 

C

 

A

 

I : M4

×

115

 