ABB | SACE Tmax XT
Protections | 5 - Power protections
63 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
OQ Protection
Q27
t
t27
Q
OQ
Function
The protection sends a TRIP command if one or more of the reactive power values detected by the unit
exceed threshold Q27 for longer than t27.
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 80)
• the graph with trip curve (page 93)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
OFF
Threshold Q27
Establishes the value that activates the protection.
The value is given as both absolute value (kVAR) and relative value
(Sn) and can be set within the range: 0.4 Sn to 2 Sn in 0.001 Sn steps
1 Sn
Time t27
This is the trip time of the protection; the value is given in seconds and
can be set within a range: 0.5 s to 100 s, in 0.5 s steps
1 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 75).
OP Protection
P26
t
t26
P
OP
Function
The protection sends a TRIP command if one or more of the active power values detected by the unit exceed
threshold P26 for longer than t26.
To check and simulate the trip times in relation to all the parameters, please consult:
• summary table of the protections with the operating characteristics (page 80)
• the graph with trip curve (page 93)
Parameters
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the
parameters menu
OFF
Trip Enable
Activates/deactivates transmission of the open command: if disabled,
the alarm and exceedance of protection time are only managed as
information
OFF
Threshold P26
Establishes the value that activates the protection.
The value is given as both absolute value (kW) and relative value (Sn)
and can be set within the range: 0.4 Sn to 2 Sn in 0.001 Sn steps
1 Un
Time t26
This is the trip time of the protection; the value is given in seconds and
can be set within a range: 0.5 s to 100 s, in 0.5 s steps
1 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or by
connection to the system bus (page 75).