ABB | SACE Tmax XT
Additional functions | 3 - IPS Interface protections
125 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
3 - IPS Interface protections
Description
The
IPS Interface protection
function allows faults to be managed in installations which are able to function
thanks to the energy produced by renewable and local energy sources, especially the absence of power
supply, e.g. caused by a fault on the MV voltage side.
The function is available for all the Ekip Hi-Touch Trip units.
All the parameters and measurements of the function are available via Ekip Connect; however, the Trip unit
allows protection
59 S1, V DIR, V INV
and control thresholds
Voltage stability
,
Frequency stability
and
F W1
to be set, as described below.
IMPORTANT: consult the Technical catalog or White paper of the function for full
details (page 4, 14).
Protection 59.S1 [ANSI 59S1]
The protection sends a TRIP command if the maximum mean value of the three line-to-line voltages,
calculated in a 10-minute floating menu, exceeds the threshold for longer than the set time.
The
Protections-Advanced
menu includes the protection submenu in which the parameters can be entered:
Parameter
Description
Default
Enable
Activates/deactivates the protection and its availability in the parameters
menu
Off
Trip Enable
Activates/deactivates transmission of the open command: if disabled, the
alarm and exceedance of protection time are only managed as information
Off
Threshold
Establishes the value that activates the protection.
The value is given as both absolute value (Volts) and relative value (Un) and
can be set within the range: 1 Un to 1.3 Un, in 0.05 Un steps
1,1 Un
Time
This is the trip time of the protection; the value is given in seconds and can
be set within a range: 3 s to 999 s, in 3 s steps
3 s
Limitations and additional functions
The block functions can also be accessed by means of the service connector (via Ekip Connect) or
communication via system bus (page 75).
Protection V DIR [ANSI 27VD]
If the positive sequence measured by the Trip unit exceeds or falls below threshold Upos (depending on the
direction set), the corresponding alarm will be activated (no TRIP).The
Protections-Advanced
menu includes
the protection submenu in which the parameters can be entered:
Parameter
Description
Default
Enable
Activates/deactivates the control threshold of the parameters and their
availability in the menu
Off
Direction
Defines whether sequence monitoring is performed after the measured
sequence has dropped (Down) or been exceeded (Up)
Down
Threshold
Establishes the value that activates the alarm.
The value is given as both absolute value (Volts) and relative value (Un) and
can be set within the range: 0.1 Un to 1.5 Un in 0.05 Un steps
0,8 Un
Protection V INV [ANSI 59VI]
If the negative sequence measured by the Trip unit exceeds or falls below threshold Uneg, the corresponding
alarm will be activated (no TRIP).
The
Protections-Advanced
menu includes the protection submenu in which the parameters can be entered:
Parameter
Description
Default
Enable
Activates/deactivates monitoring of the parameters and their availability in
the menu
Off
Threshold
Establishes the value that activates the alarm. The value is given as both
absolute value (Volts) and relative value (Un) and can be set within the range:
0.05 Un to 0.5 Un in 0.05 Un steps
0,05 Un