ABB | SACE Tmax XT
External accessories | 14 - Ekip Synchrocheck
167 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Continued from the previous page
Parameter
Description
Default
Secondary voltage
Secondary voltage of the transformer; the value is given as absolute value
(Volts) and can be set within the range: 100 V to 120 V in variable steps.
100 V
Concatenated Ref
Line-to-line voltage entering the module among the 3 installation voltages U12
Contact Type
Defines the rest status of the contact with synchronism not present
between: open (NO) and closed (NC)
NO
(1) parameter not available with busbar active and Auto deadbar detect= Manual
(2) with dead busbar and configuration: Reversed, the roles of the internal and external voltages are reversed
(3) 10% hysteresis is applied to the minimum voltage condition: once reached, the condition is lost if the
voltage drops below 90% of the set limit
(4) parameter not available with dead busbar and Auto deadbar detect= Manual
Remote configurations
Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter
Description
Default
Frequency
check
Activates (ON) or deactivates (OFF) frequency control for synchronism
assessment
ON
Phase check
Activates (ON) or deactivates (OFF) phase control for synchronism assessment ON
Evaluate CB
status
Activates (YES) or deactivates (NO) circuit-breaker open status control for
synchronism assessment
NOTE
:
fourth synchronism condition with busbar active; second
synchronism condition with dead busbar
NO
Minimum
matching time
With active busbar, minimum time within which the
Delta Phase
condition must
be obtained
The value is given in seconds and can be set within the range: 100 ms to 3 s,
in 10 ms steps
NOTE
:
this is not a synchronism condition, but a parameter allowing a
discrimination to be made between correct and incorrect combinations of
the Delta Frequency and Delta Phase conditions. Owing to worst case
latencies, the time that effectively elapses before synchronism is
recognized may be longer than the set time (approx. 20 ms)
100 ms
Measurements
The specific measurement area will activate in the
Measurements
-
Synchrocheck
menu if the
Ekip
Synchrocheck
module is detected correctly by Ekip Touch.
Measurement
Description
Module
• Ok = Synchronism conditions fulfilled
• Not Ok = Synchronism conditions not fulfilled or function disabled
Frequency
• Ok = Synchronism condition regarding frequencies fulfilled
• Not Ok = Synchronism condition regarding frequencies not fulfilled or synchronism
function disabled, or frequencies outside measuring range limits.
• --- = Synchronism condition regarding frequencies not available (example: for
operation with dead busbar)
Voltage
• Ok = Synchronism conditions regarding voltages fulfilled.
• Not Ok = Synchronism conditions regarding voltages not fulfilled or synchronism
function disabled
Phase
• Ok = Synchronism condition regarding phase difference fulfilled
• Not Ok = Synchronism condition regarding phase difference not fulfilled or
synchronism function disabled, or frequencies outside measuring range limits
• --- = Synchronism condition regarding phase difference not available (example: for
operation with dead busbar)
Ext Side Voltage
(1)
• Voltage measured by
Ekip Synchrocheck
given in Volts
• .... = measurement DC or less than 1 VAC
• --- = measurement not available (example: because synchronism function is
disabled)
Continued on the next page