ABB | SACE Tmax XT
182 | © 2019 ABB | 1SDH002039A1002 - ECN000093027 - Rev. A
Internal accessories | 4 - Ekip Com EtherNet/IP TM
Power supply
Ekip Com EtherNet/IP
TM
is supplied directly by the
Ekip Touch
module to which it is connected.
NOTE:
communication between Ekip Touch and the module is interrupted in the absence of
auxiliary power supply
Configurations via menu
Local bus activation, which is essential for starting the communication between module and Ekip Touch, is
available in the
Settings
menu (page 33).
The following communication parameters can be configured if the module has been correctly detected by
Ekip Touch in the
Settings
-
Modules
menu:
Parameter
Description
Default
Static IP address ON
Defines whether the module has a dynamic (Off) IP address
or static (On) IP address
Se = On all the associated parameters are enabled
Off
Static address IP address
Enables the static IP to be selected
0.0.0.0
Static Network Mask
Enables the subnet mask to be selected
0.0.0.0
Static Gateway address
When there are several subnets, enables the IP address of
the node to which the module is connected to be selected
0.0.0.0
Information in menu
The following information will be available in the
About
-
Modules
menu if Ekip Touch has detected the module
correctly:
Parameter
Description
SN and version
Identifier and SW version of the module
IP address
Address of the module, assigned to the module by a DHCP server at the time
of connection to the network in the case of configuration with a dynamic IP, or
can be set via the menu in the event of a static IP.
NOTE
:
without a DHCP server, the module automatically adopts a
random IP address within the 169.254.xxx.xxx
range
Network Mask
Subnet mask; identifies the method for recognizing the subnet to which the
modules belong and enables modules to be searched for within a defined set
of recipients.
Gateway address
IP address of the node to which the module is connected, in the presence of
several subnets
MAC address
Address assigned by ABB, with OUI (Organizationally Unique Identifier) equal to
ac:d3:64, which uniquely identifies the manufacturer of an Ethernet device
Remote configurations
Additional parameters can be accessed via the service connector (via Ekip Connect) or via a system bus
communication:
Parameter
Description
Default
Enable IEEE 1558
Allows the IEEE 1588 protocol for distribution of the clock
and synchronization signal to be enabled
(NOTE)
Off
IEEE 1558 Master
Enables the module to be set up as a master in the the
network segment to which it belongs (synchronization
clock).
Off
IEEE 1558 Delay mechanism
Allows the data exchange mode between module and
master, either Peer-to-Peer or End-to-End, to be selected.
End-to-End
Enable client SNTP
Allows the SNTP protocol for distribution of the clock and
synchronization signal to be enabled
(NOTE)
.
Off
ANTP Server address
Allows the network server that supplies the SNTP to be set. 0.0.0.0
Time zone
Defines the time zone to be used for synchronism
+00:00
Daylight Saving Time
Used to select whether daylight saving time is present (ON)
or not (OFF) in the country to which the synchronization
time refers
Off
NOTE:
Enable IEEE 1588 and Enable SNTP client must not be enabled at the same time
Содержание SACE Tmax XT5
Страница 2: ...ABB SACE Tmax XT 2 2019 ABB 1SDH002039A1002 ECN000093027 Rev A ...
Страница 4: ...II 2019 ABB SACE Tmax XT 1SDH002039A1002 ECN000093027 Rev A ...
Страница 204: ...ABB SACE Tmax XT 202 2019 ABB 1SDH002039A1002 ECN000093027 Rev A Other accessories 5 Testing and Programming ...
Страница 205: ...1SDH002039A1002 ECN000093027 Rev A ...