Table 5.1.4.7.-8
SGR1...SGR8 (Continued)
Switch
Function
Default setting
SGR1...SGR3
SGR4...SGR5
SGR6...SGR8
SGR1...8/11
Pickup signal from element 59N-2
0
1
0
SGR1...8/12 Trip signal from element 59N-2
1
0
0
SGR1...8/13 External trip signal
0
0
0
Σ
SGR1...8
2730
1365
0
a)
If the optional I/O module has not been installed, dashes are shown on the LCD and
“
9999
”
when the parameter is read via the SPA
bus.
SGL1...SGL8
The signals are routed to LED1 with the switches of switchgroup SGL1, to
LED2 with those of SGL2, and so forth.
Table 5.1.4.7.-9
SGL1...SGL8
Switch
Function
Default setting
SGL1...8/1
Trip signal from element 59P-1
0
SGL1...8/2
Trip signal from element 59P-2 or 47
0
SGL1...8/3
Trip signal from element 27P-1
0
SGL1...8/4
Trip signal from element 27P-2 or 27D
0
SGL1...8/5
Trip signal from element 59N-1
0
SGL1...8/6
Trip signal from element 59N-2
0
SGL1...8/7
Trip lockout signal
0
SGL1...8/8
DI1 signal
0
SGL1...8/9
DI2 signal
0
SGL1...8/10
DI3 signal
0
SGL1...8/11
DI4 signal
0
SGL1...8/12
DI5 signal
0
Σ
SGL1...SGL8
0
New trip target timer
The new trip target timer can be configured to allow a second trip target on
the LCD. When several protection elements trip, the first trip target is
displayed until the time, as specified by the
NEW TRIP IND.
setting value,
has expired. After this, a new trip target can displace the old one. The basic
protection functions are not affected by the
NEW TRIP IND.
setting.
44
REU 610
Voltage Relay
Technical Reference Manual - ANSI Version
1MRS755972
Содержание REU 610
Страница 1: ...Voltage Relay REU 610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 10: ...10 ...
Страница 128: ...128 ...
Страница 138: ......
Страница 139: ......