Table 5.1.15.2.-14Fault record (Continued)
Address
Signal name
Range
Comment
611
Residual voltage U
n
0...200
0...200% U
n
(VT)
612
Maximum pick-up phase-to-phase voltage
0...200
0...2
×
U
n
(VT)
613
Minimum pick-up phase-to-phase voltage
0...200
0...2
×
U
n
(VT)
614
Maximum pick-up negative phase-sequence voltage
U
2
0...200
0...2
×
U
n
(VT)
b)
615
Minimum pick-up positive phase-sequence voltage
U
1
0...200
0...2
×
U
n
(VT)
b)
616
Maximum residual voltage U
n
0...200
0...200% U
n
(VT)
617
Pickup duration of element 59P-1
0...100
0...100%
618
Pickup duration of element 59P-2
0...100
0...100%
619
Pickup duration of element 27P-1
0...100
0...100%
620
Pickup duration of element 27P-2
0...100
0...100%
621
Pickup duration of element 59N-1
0...100
0...100%
622
Pickup duration of element 59N-2
0...100
0...100%
623
Pickup duration of external trip
0...100
0...100%
a)
Readable and writeable register.
b)
If not in use, the value 655 is returned.
Structure 3
This structure contains Modbus event records. Refer to Event records earlier
in this section for the reading method.
Table 5.1.15.2.-15Event record
Address
Signal name
Range
Comment
671
Latest selection code
a)
1...3
1 = read oldest unread
record
2 = read oldest stored record
3 = clear Modbus event
buffer
-1...-99
-1...-99 = move to the nth
newest record
672
Sequence number
1...255
673
Unread records left
0...99
674
Time stamp of the event, date
2 bytes: YY.MM
675
Time stamp of the event, date and time
2 bytes: DD.HH
676
Time stamp of the event, time
2 bytes: MM.SS
677
Time stamp of the event, time
0...999
0...999 ms
678
Event data
See Table 5.1.15.2.-16 for
Modbus DI-point events and
Table 5.1.15.2.-17 for
informative events
679
74
REU 610
Voltage Relay
Technical Reference Manual - ANSI Version
1MRS755972
Содержание REU 610
Страница 1: ...Voltage Relay REU 610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 10: ...10 ...
Страница 128: ...128 ...
Страница 138: ......
Страница 139: ......