Table 5.2.3.-10 Environmental tests and conditions (Continued)
Dry heat test
According to IEC 60068-2-2
Dry cold test
According to IEC 60068-2-1
Damp heat test, cyclic
According to IEC 60068-2-30
Table 5.2.3.-11
Electromagnetic compatibility tests
EMC immunity test level meets the requirements listed below:
1 MHz burst disturbance test, class III
According to IEC 60255-22-1
-Common mode
2.5 kV
-Differential mode
1.0 kV
Electrostatic discharge test, class IV
According to IEC 61000-4-2, IEC 60255-
22-2 and ANSI C37.90.3-2001
-For contact discharge
8 kV
-For air discharge
15 kV
Radio frequency interference tests:
-Conducted, common mode
According to IEC 61000-4-6 and
IEC 60255-22-6 (2000)
10 V (rms), f = 150 kHz...80 MHz
-Radiated, amplitude-modulated
According to IEC 61000-4-3 and
IEC 60255-22-3 (2000)
10 V/m (rms), f = 80...1000 MHz
-Radiated, pulse-modulated
According to the ENV 50204 and
IEC 60255-22-3 (2000)
10 V/m, f = 900 MHz
Fast transient disturbance tests
According to IEC 60255-22-4 and
IEC 61000-4-4
-Power outputs, energizing inputs, power
supply
4 kV
-I/O ports
2 kV
Surge immunity test
According to IEC 61000-4-5
-Power outputs, energizing inputs, power
supply
4 kV, line-to-earth
2 kV, line-to-line
-I/O ports
2 kV, line-to-earth
1 kV, line-to-line
Power frequency (50 Hz) magnetic field
IEC 61000-4-8
300 A/m continuous
Voltage dips and short interruptions
According to IEC 61000-4-11
30%/10 ms
60%/100 ms
60%/1000 ms
>95%/5000 ms
Electromagnetic emission tests
According to the EN 55011
-Conducted, RF-emission (Mains
terminal)
EN 55011, class A, IEC 60255-25
-Radiated RF-emission
EN 55011, class A, IEC 60255-25
CE approval
Complies with the EMC directive 89/336/
EEC and the LV directive 73/23/EEC
126
REU 610
Voltage Relay
Technical Reference Manual - ANSI Version
1MRS755972
Содержание REU 610
Страница 1: ...Voltage Relay REU 610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 10: ...10 ...
Страница 128: ...128 ...
Страница 138: ......
Страница 139: ......