105
Table 5.1.17.1.-1 Event masks
Event mask
Code
Setting range
Default setting
V155
E31...E34
0...15
1
1V155
1E1...1E16
0...65535
21845
1V156
1E17...1E24
0...255
85
1V157
1E25...1E30
0...63
1
2V155
2E1...2E16
0...65535
3
2V156
2E17...2E26
0...1023
0
Channel 0
Events always included in the event reporting:
Table 5.1.17.1.-2 Event codes E1...E4
Channel
Event
Description
0
E1
IRF
0
E2
IRF disappeared
0
E3
Warning
0
E4
Warning disappeared
Table 5.1.17.1.-3 Event codes E50...E51
Channel
Event
Description
0
E50
Relay restart
0
E51
Event buffer overflow
Events possible to mask out:
Table 5.1.17.1.-4 Event codes E31...E34
Channel
Event
Description
Weight-
ing
factor
Default
value
0
E31
Disturbance recorder triggered
1
1
0
E32
Disturbance recorder memory cleared
2
0
0
E33
HMI password opened
4
0
0
E34
HMI password closed
8
0
Default value of event mask V155
1
1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
REU 610