41
SGB1...SGB5
The DI1 signal is routed to the functions below with the switches of
switchgroup SGB1, the DI2 signal with those of SGB2, and so forth.
Table 5.1.4.7.-7
SGB1...SGB5
Switch
Function
Default setting
SGB1...5/1
*
0 = targets are not cleared by the digital input signal
*
1 = targets are cleared by the digital input signal
0
SGB1...5/2
*
0 = targets are not cleared and latched output contacts are not unlatched by the digital input
signal
*
1 = targets are cleared and latched output contacts are unlatched by the digital input signal
0
SGB1...5/3
*
0 = targets and memorized values are not cleared and latched output contacts are not
unlatched by the digital input signal
*
1 = targets and memorized values are cleared and latched output contacts are unlatched by
the digital input signal
0
SGB1...5/4
Switching between setting groups 1 and 2 by using the digital input
*
0 = the setting group cannot be changed using the digital input
*
1 = the setting group is changed by using the digital input. When the digital input is
energized, setting group 2 is activated, if not, setting group 1 is activated.
When SGB1...5/4 is set to 1, it is important that the switch has the same setting
in both setting groups.
0
SGB1...5/5
Time synchronization by the digital input signal
0
SGB1...5/6
External tripping by the digital input signal
0
SGB1...5/7
External triggering of the CBFAIL by the digital input signal
0
SGB1...5/8
External triggering of the trip lockout by the digital input signal
0
SGB1...5/9
Resetting of the trip lockout by the digital input signal
0
SGB1...5/10
Blocking of tripping of element 59P-1 by the digital input signal
0
SGB1...5/11
Blocking of tripping of element 59P-2 or 47 by the digital input signal
0
SGB1...5/12
Blocking of tripping of element 27P-1 by the digital input signal
0
SGB1...5/13
Blocking of tripping of element 27P-2 or 27D by the digital input signal
0
SGB1...5/14
Blocking of tripping of element 59N-1 by the digital input signal
0
SGB1...5/15
Blocking of tripping of element 59N-2 by the digital input signal
0
Σ
SGB1...5
0
SGR1...SGR8
The pickup, trip and alarm signals from the protection elements and the
external trip signal are routed to the output contacts with the switches of
switchgroups SGR1...SGR8.
The signals are routed to PO1...PO3 with the switches of switchgroup
SGR1...SGR3 and to SO1...SO5 with those of SGR4...SGR8.
1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
REU 610
Содержание REU 610
Страница 1: ...Voltage Relay REU 610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 10: ...10 ...
Страница 128: ...128 ...
Страница 138: ......
Страница 139: ......