Table 5.1.4.7.-5
SGF4 (Continued)
Switch
Function
Default setting
SGF4/7
Start and trip criteria for element 27P-1
a)
*
0 = element operates when one of the phase-to-phase voltages falls below the set pickup
value.
*
1 = element operates when all the phase-to-phase voltages fall below the set value.
0
SGF4/8
Start and trip criteria for element 27P-2
a)
*
0 = element operates when one of the phase-to-phase voltages falls below the set pickup
value.
*
1 = element operates when all the phase-to-phase voltages fall below the set value.
This switch has no effect if element 27P-2 is based on positive-phase-
sequence calculation.
1
SGF4/9
27P-1 Alarm mode selection
*
0 = normal operation of element 27P-1, used for tripping purposes
*
1 = element 27P-1 operates as 27P-1 Alarm.
The alarm signal is routed to element 27P-1 trip in relay matrix, and the pickup signal of
element 27P-1 is inhibited. When the alarm signal is active, the pickup LED is lit.
0
SGF4/10
Internal blocking of pickup and trip of element 47 when one of the measured phase-to-phase
voltages falls below 0.15
×
U
n
(VT).
*
0 = internal blocking of pickup and trip of element 47
*
1 = no internal blocking of pickup and trip of element 47
0
Σ
SGF4
128
a)
If the switch SGF4/1 is set to 1, the switches SGF4/5...8 are overridden. Thereby all the elements use only phaseU
ab
as input, and
other phases are not checked or used.
Table 5.1.4.7.-6
SGF5
Switch
Function
Default setting
SGF5/1
Selection of the latching feature for programmable LED1
0
SGF5/2
Selection of the latching feature for programmable LED2
0
SGF5/3
Selection of the latching feature for programmable LED3
0
SGF5/4
Selection of the latching feature for programmable LED4
0
SGF5/5
Selection of the latching feature for programmable LED5
0
SGF5/6
Selection of the latching feature for programmable LED6
0
SGF5/7
Selection of the latching feature for programmable LED7
0
SGF5/8
Selection of the latching feature for programmable LED8
*
When the switch is in position 0 and the signal routed to the LED is reset, the programmable
LED is cleared.
*
When the switch is in position 1, the programmable LED remains lit although the signal
routed to the LED is reset.
A latched programmable LED can be cleared either via the HMI, a digital input or the serial bus.
0
Σ
SGF5
0
40
REU 610
Voltage Relay
Technical Reference Manual - ANSI Version
1MRS755972