Table 5.1.15.2.-13Mapping of Modbus data: control points
Description
HR/IR address
(.bit)
DI/Coil bit
address
Writeable
Value range Comment
LED reset
501
W
1
1 = LED reset
a)
a)
Coil area, only writeable.
Structure 1
The status registers contain information on unread fault and event records,
and relay status. The registers are arranged as in Fig. 5.1.15.2.-2 below.
401
402
403
15
8
7
0
Reserved
Warning code
IRF code
Reserved
FR ER
SP MP
A040333
Fig. 5.1.15.2.-2
Status registers
When the value of the FR/ER bit is 1, there is one or several unread fault/
event records. If time synchronization is realized via a digital input, either the
SP (second-pulse) or MP (minute-pulse) bit will be activated.
Refer to Table 5.1.18.-1 for IRF codes and Table 5.1.18.-2 for warning codes.
Structure 2
This structure contains data recorded during a fault sequence. Refer to Fault
records earlier in this section for the reading method.
Table 5.1.15.2.-14Fault record
Address
Signal name
Range
Comment
601
Latest selection code
a)
1...2
1 = read oldest unread
record
2 = read oldest stored
record
602
Sequence number
1...255
603
Unread records left
0...6
604
Time stamp of the recorded data, date
2 bytes: YY.MM
605
Time stamp of the recorded data, date and time
2 bytes: DD.HH
606
Time stamp of the recorded data, time
2 bytes: MM.SS
607
Time stamp of the recorded data, time
0...999
0...999 ms
608
Phase-to-phase voltage U
ab
0...200
0...2
×
U
n
(VT)
609
Phase-to-phase voltage U
bc
0...200
0...2
×
U
n
(VT)
610
Phase-to-phase voltage U
ca
0...200
0...2
×
U
n
(VT)
1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
REU 610