79
Configurable, range from 0 to 255 with
primary data link layer retransmission
count
Configurable, range from 0 to 255 with
application layer retransmission count
Requires Data Link Layer Confirmation:
Configurable, with confirmation type selector, default NO ACK
Requires Application Layer Confirmation
Configurable with confirmation type selector when reporting Event Data (Slave
devices only)
Always after response to reset request
Always when sending multi-fragment responses (Slave devices only)
Configurable, with confirmation type selector
Timeouts while waiting for:
Data Link Confirm
Configurable with primary data link layer
timeout, not relevant when NO ACK
Complete Appl. Fragment
No, multi-fragment application frames not
supported
Application Confirm
Configurable with application layer
timeout
Complete Appl. Response
No, not relevant in slave
Sends/Executes Control Operations
WRITE Binary Outputs
Never
SELECT/OPERATE
Never
DIRECT OPERATE
Never
DIRECT OPERATE - NO ACK
Never
Count
Never
Code
Never
Trip/Close
Never
Pulse On
Never
Queue
Never
Clear Queue
Never
FILL OUT THE FOLLOWING ITEMS FOR SLAVE DEVICES ONLY:
Reports Digital Input Change Events
when no specific variation requested
Reports time-tagged Digital Input Change
Events when no specific variation
requested
Never
Never
Only time-tagged
Binary Input Change With Time
Only non-time-tagged
Binary Input Change With Relative
Time
Configurable to send both, one or the
other (depends on default variation)
Configurable, depends on objects
basic variation (variation used at
initialization)
Sends Unsolicited Responses
Sends Static Data in Unsolicited
Responses
Never
Never
Configurable
When Device Restarts
Only certain objects
When Status Flags Change
1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
REU 610
Содержание REU 610
Страница 1: ...Voltage Relay REU 610 Technical Reference Manual ANSI Version ...
Страница 2: ......
Страница 6: ...6 ...
Страница 10: ...10 ...
Страница 128: ...128 ...
Страница 138: ......
Страница 139: ......