99
Table footnotes from previous page
a)
When the value is 1, the digital input is energized.
b)
If the optional I/O module has not been installed, a dash is shown on the LCD and "9" when the
parameter is read via the SPA bus.
Each protection element has its internal output signal. These signals can be
read with parameters
O1
...
O15
and the recorded functions with parameters
O61
...
O75
. The state of the output contacts can be read or changed with
parameters
O41
...
O49
and the recorded functions read with parameters
O101
...
O109
.
Table 5.1.17.-9 Output signals
Status of the
protection
elements
State of element
(R), channel 0
Recorded
functions (R),
channel 0
Value
Pickupof element
59P-1
O1
O61
0/1
Trip of element 59P-
1
O2
O62
0/1
Pickupof element
59P-2 or 47
O3
O63
0/1
Trip of element 59P-
2 or 47
O4
O64
0/1
Pickupof element
27P-1
O5
O65
0/1
Trip of element 27P-
1
O6
O66
0/1
Pickupof element
27P-2 or 27D
O7
O67
0/1
Trip of element 27P-
2 or 27D
O8
O68
0/1
Pickupof element
59N-1
O9
O69
0/1
Trip of element 59N-
1
O10
O70
0/1
Pickupof element
59N-2
O11
O71
0/1
Trip of element 59N-
2
O12
O72
0/1
External trip
O13
O73
0/1
Trip lockout
O14
O74
0/1
CBFAIL trip
O15
O75
0/1
1MRS755972
Voltage Relay
Technical Reference Manual - ANSI Version
REU 610