Table 5.1.4.7.-2
SGF1 (Continued)
Switch
Function
Default setting
SGF1/3
Selection of the latching feature for PO3
*
When the switch is in position 0 and the measuring signal which caused the trip falls below
the set pickup value, the output contact returns to its initial state.
*
When the switch is in position 1, the output contact remains active although the measuring
signal which caused the trip falls below the set pickup value.
A latched output contact can be unlatched either via the HMI, a digital input or the serial bus.
0
SGF1/4
Minimum pulse length for SO1 and SO2 and optional SO3, SO4 and SO5
*
0 = 80 ms
*
1 = 40 ms
0
SGF1/5
Minimum pulse length for PO1, PO2 and PO3
*
0 = 80 ms
*
1 = 40 ms
The latching feature being selected for PO1, PO2 and PO3 overrides this
function.
0
SGF1/6
CBFAIL
*
0 = CBFAIL is not in use
*
1 = the signal to PO1 pickups a timer which generates a delayed signal to PO2, provided that
the fault is not cleared before the CBFAIL operate time has elapsed
0
SGF1/7
Trip lockout function
*
0 = the trip lockout function is not in use. PO3 works as a normal power ouput relay.
*
1 = the trip lockout function is in use. PO3 is dedicated to this function.
0
SGF1/8
External fault warning
*
When the switch is in position 1, the warning signal from the trip-circuit supervision is routed
to SO2.
0
Σ
SGF1
0
Table 5.1.4.7.-3
SGF2
Switch
Function
Default setting
SGF2/1
Operation mode of the pickup target of element 59P-1
a)
0
SGF2/2
Operation mode of the trip target of element 59P-1
1
SGF2/3
Operation mode of the pickup target of element 59P-2 or 47
a)
0
SGF2/4
Operation mode of the trip target of element 59P-2 or 47
1
SGF2/5
Operation mode of the pickup target of element 27P-1
a)
0
SGF2/6
Operation mode of the trip target of element 27P-1
1
SGF2/7
Operation mode of the pickup target of element 27P-2 or 27D
a)
0
SGF2/8
Operation mode of the trip target of element 27P-2 or 27D
1
SGF2/9
Operation mode of the pickup target of element 59N-1
a)
0
SGF2/10
Operation mode of the trip target of element 59N-1
1
SGF2/11
Operation mode of the pickup target of element 59N-2
a)
0
SGF2/12
Operation mode of the trip target of element 59N-2
*
0 = the trip target is automatically cleared after the fault has disappeared.
*
1 = latching. The trip target remains active although the fault has disappeared.
1
Σ
SGF2
2730
38
REU 610
Voltage Relay
Technical Reference Manual - ANSI Version