background image

Unit 8 IDA Business Park, Whitestown, Tallaght, Dublin 24, Ireland. 

 Telephone: 353 1 462 2585.  Telefax: 353 1 462 2587.  E-mail: [email protected]   Web: www.actrl.com

ACTLAN Interface Configuration

 

ACTWin Pro Software

1. Ask the network administrator to supply you with a permanent IP network address.

2. Connect a PC directly to the ACTLAN and run HyperTerminal at 9600 baud, no parity, 1 stop.

3. Power up the ACTLAN and 

immediately

 hit 3 lowercase "x" (xxx).

4. Hit the Enter key to go inte Setup Mode.

5. Select 0 and follow the prompts until you get to IP address.

6. Enter the new IP address.

7. If the ACT controllers are on a different LAN segment to the ACTWin Pro PC, then a Gateway

    Address is required. Check with the network administrator for the IP address of the router.

8. A Netmask may also be required. Check with the  network administrator.  

9. Follow the prompts to come back to the Setup Menu.

10. Select 1 to configure the RS232 channel.

11. Set up the following parameters as follows:

 

Baud Rate   

 

 

  

9600 

 

I/F Mode  

 

 

 

 

 

 

 

        

4C for Direct Connect,4F for Network

 

Flow 

 

 

 

 

 

 

 

      

  

 

    00   

 

Port  

  

  

 

 

 

 

       

10001

 

Connect Mode   

 

  

C0   

    Disconnect Mode  

00

 

Flush Mode   

  

  

80   

     Pack Control  

 

 

 

 

 

       

00

 

Remote IP Address     

none

12. Return to the Setup Menu and select 9 to save the settings.

13. Finally test the setup by connecting to the IP address using a Web browser or 'Pinging'.

14. From ACTWin Pro, enter the new IP address into the location manager for the site.

18-00026 Issue 4

ser
ial

10B

ASE-T

9-30v

link

net 

Tx/Rx

collision

diagnosit

c

sta
tus

LAN/WAN

A B 0V

TX

RX

NETWORK

DOORS

A

B
0V

SERIAL/PRINTER

0V

DTR

DB25 Male

(Rear View)

7

3 2

Max cable length is 5m using standard 

alarm cable or 30m using twin twisted-pair 

(use 0V in each pair)

Connections for 25 Way male Connector

RX = Pin 3

TX = Pin 2

0V = Pin 7

ACT 2000

                                         TCP/IP Configuration

 

Connections for Direct Connect

Connections for Network

1. Connect cable directly to 
ACT1000/2000 and LAN device
2. In Communications Menu Set:
 

 

 

Address = 1 

 

 

 

Direct Conn = Y

ACT 2000

1. Connect LAN RS-485 cable to 
NETWORK terminals on the 
controller and LAN Interface
2. In ACT1000/2000 Communications
Menu set  the controller Address  and
set  Direct Conn = N

A B 0V

NETWORK

DOORS

A

B
0V

7

22 21

15 14

DB25 Male

(Rear View)

A = Pin 14

B = Pin 15

0V = Pin 7

Pin 14 = Pin 21

Pin 15 = Pin 22

ACT, Unit C1, South City Business Centre, Tallaght, Dublin 24, Ireland.                       www.accesscontrol.ie 

Telephone: 353 1 466 2570      UK Lo-Call 0845-300 5204       Fax: 353 1 452 0427        E-mail: [email protected] 

Отзывы: