LOAccCurrPwr: Lockout limit setting for accumulated energy.
SpChAlmTime: Time delay for spring charging time alarm.
tDGasPresAlm: Time delay for gas pressure alarm.
tDGasPresLO: Time delay for gas pressure lockout.
DirCoef: Directional coefficient for circuit breaker life calculation.
RatedOperCurr: Rated operating current of the circuit breaker.
RatedFltCurr: Rated fault current of the circuit breaker.
OperNoRated: Number of operations possible at rated current.
OperNoFault: Number of operations possible at rated fault current.
CBLifeAlmLevel: Alarm level for circuit breaker remaining life.
AccSelCal: Selection between the method of calculation of accumulated energy.
OperTimeDelay: Time delay between change of status of trip output and start of main contact
separation.
5.4
Disturbance report DRPRDRE
IP14584-1 v2
5.4.1
Identification
M16055-1 v9
Function description
IEC 61850 identification
IEC 60617
identification
ANSI/IEEE C37.2
device number
Disturbance report
DRPRDRE
-
-
Disturbance report
A4RADR
-
-
Disturbance report
B1RBDR - B22RBDR
-
-
5.4.2
Application
M12152-3 v10
To get fast, complete and reliable information about disturbances in the primary and/or in the
secondary system it is very important to gather information. It is also important having a
continuous event-logging to be able to monitor in an overview perspective. These tasks are
accomplished by the disturbance report function DRPRDRE and facilitate a better
understanding of the power system behavior and related primary and secondary equipment
during and after a disturbance. An analysis of the recorded data provides valuable information
that can be used to explain a disturbance, basis for change of IED setting plan, improve
existing equipment, and so on. This information can also be used in a longer perspective when
planning for and designing new installations, that is, a disturbance recording could be a part
of Functional Analysis (FA).
Disturbance report DRPRDRE, always included in the IED, acquires sampled data of all selected
analog and binary signals connected to the function blocks that is,
•
10 internal derived analog signals, and
•
352 binary signals
1MRK 511 445-UEN B
Section 5
Monitoring
Switchgear control unit SAM600-IO
47